2020-03-16 14:25:35 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #20020774 |
| 3/16/20 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW |
| AC SYSTEMS- SECTION C403.2.1 FBC EC AND SECTION 312.1 |
| FBC M. |
| |
| 2) COMMISSIONING OF THE MECHANICAL SYSTEMS IS REQUIRED |
| PER SECTION C408.2 FBC EC. SUBMIT A COMMISSIONING PLAN |
| AS OUTLINED IN SECTION C408.2.1 AND DESCRIBED IN |
| SECTIONS C403.2.2- C408.2.3.3, OR PLACE NOTES ON THE |
| PLAN TO VERIFY COMPLIANCE. PLEASE NOTE THAT COPIES OF |
| THE COMMISSIONING REPORT SHALL BE PROVIDED TO THE |
| BUILDING OWNERSHIP, AND TO THE WPB BUILDING DEPARTMENT |
| FOR FINAL APPROVAL. |
| |
| 3) M1.1: PROVIDE AUTOMATICALLY CONTROLLED SHUTOFF |
| DAMPERS FOR THE O/A INTAKE DUCTS- SECTION C403.2.4.3 |
| FBC EC. |
| |
| 4) M1.1: USING THE TRANE DUCTULATER FOR CALCULATING |
| DUCT SIZES, THE 36/14 SUPPLY TRUNKS AND ALL OVER BRANCH |
| AND FLEX DUCT SIZES ARE UNDERSIZED WHEN USING A |
| FRICTION LOSS OF 0.1 IN INCHES OF WATER. WHAT FRICTION |
| LOSS WAS USED TO CALULATE THE DUCT SIZES? |
| |
| 5) PROVIDE SITE SPECIFIC WIND LOAD ENGINEERING FOR |
| INSTALLATION OF THE RTU'S- SECTION 301.15 FBC M. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |