Plan Review Notes For Permit 20020746 |
Permit Number |
20020746 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-02-25 18:04:03 | 02/25/2020 PLUMBING 1ST REVIEW **DENIED** WITH COMMENTS | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | 1. AN ELECTRICAL PERMIT IS REQUIRED FOR BY A LICENSED | | CONTRACTOR PER THE WPB AMENDMENTS TO THE FBC SEC. | | 105.1. | | 2. THIS HEATER IS NOT MADE FOR OUTSIDE ELEMENTS AND IT | | IS NOT A UNIT USED TO HEAT SWIMMING POOLS PLEASE | | PROVIDE A UNIT THAT DOES AND SUBMIT DOCUMENTATION THAT | | THE POOL HEATER COMPLIES WITH THE 2017 FBC-ENERGY SEC. | | R403.10.1. | | 3. PLEASE PROVIDE 2 COPIES OF THE LOCATION FOR THE | | WATER HEATER DRAWN IN A PLOT OF THE HOUSE PER THE 2017 | | FBC WPB AMENDMENTS SEC. 107.3.5 MINIMUM PLAN REVIEW | | CRITERIA FOR BUILDINGS. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | LUIS A. CRESPO | | PLUMBING INSPECTOR / | | PLUMBING PLAN REVIEW | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | [email protected] | | 561-805-6720 | | |
|