2020-03-03 06:35:48ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PERMIT APPLICATION SAYS INSTALLATION OF POOL WATER
 HEATER BUT SPECS OF A TANKLESS WATER HEATER WERE
 SUBMITTED. PROVIDE PROPER CUT SHEETS FOR POOL HEATER OR
 CHANGE DESCRIPTION OF PERMIT APPPLICATION TO REFLECT
 INSTALLATION OF A TANKLESS WATER HEATER. PROPOSED WORK
 UNCLEAR. FBC 107.2.1
  
 2. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY
 THE ELECTRICAL CONTRACTOR QUALIFIER. IF THERE IS NOT
 ANY ELECTRICAL WORK INCLUDED WITH THIS PERMIT, STATE
 THAT ON PLAN. FS 471.003(2)(H); 471.025; WPB FBC
 107.2.1, 107.3.5
  
 3. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS, BOTH NEW AND EXISTING. NEC 220; FBC RE E3602.2
  
 4. VALUE LOW FOR AMOUNT OF WORK SHOWN. CONTRACT CLEARLY
 STATES LABOR ONLY "CUSTOMER SUPPLIED WATER HEATER".
 PROVIDE ACCURATE VALUE TO INCLUDE ALL MATERIALS AND
 LABOR OR VALUE WILL BE SET BY BUILDING OFFICIAL.
  
 CITY ORDINANCE AND FBC 109.3 BUILDING PERMIT
 VALUATIONS. IF, IN THE OPINION OF THE BUILDING
 OFFICIAL, THE CLAIMED VALUATION OF BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR
 PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS THE
 APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR
 BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO
 MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved