Text |
2020-04-14 10:57:42 | 1) SHT. A-411 & SHT. A-102 - DETAIL #1 - SHOW THE CLEAR |
| FLOOR SPACE FOR THE HANDICAP ACCESSIBLE WATER CLOSETS |
| ON THE ENLARGED FLOOR PLANS. COMPLY WITH 2017 |
| FBC-ACCESS. SEC. 604.3. SHOW THE LENGTH AND WIDTH |
| DIMENSIONS OF THE CLEAR FLOOR SPACE ON THE PLANS.THE |
| ONLY CLEAR FLOOR SPACE SHOWN IS FOR THE LAVATORY. 2ND |
| REQUEST. |
| 2) SHT. A-102 - WOMEN'S AND MEN'S RESTROOMS #115 & 116 |
| - A LAVATORY IS REQUIRED IN THE ACCESSIBLE TOILET |
| STALLS PER 2017 FBC-ACCESS.SEC. 604.8.1.6. 2ND REQUEST. |
| 3) SHT. A-102 - MEN'S & WOMEN'S RESTROOMS #115 & #116 - |
| THE DOORSIN THE HANDICAP ACCESSIBLE TOILET STALLS SHALL |
| BE LOCATED IN THE FRONT PARTITION OR IN THE SIDE WALL |
| OR PARTITION FARTHEST FROM THE WATER CLOSET, NOT |
| LOCATED DIRECTLY IN FRONT OF THE WATER CLOSET.2017 FBC- |
| ACCESS. SEC.604.8.1.2. 2ND REQUEST. |
| 4) THE WATER COOLER LOCATED ON THE EAST WALL OF THE |
| RESTROOM FACILITY SHALL BE A HI-LO UNIT OR 2 SEPARATE |
| UNITS COMPLYING WITH THE FBC-ACCESS. SEC. 211.1 & |
| FBC-PLUMBING SEC.410.3. THIS WAS OVERLOOKED ON THE |
| PREVIOUS REVIEW. |
| 5) SHT. A-401 - VERTICAL GRAB BARS ARE SHOWN IN THE |
| ACCESSIBILITY DETAILS. SEC. 609.4 OF THE FBC-ACCESS. |
| STATES THAT GRAB BARS SHALL BE INSTALLED IN THE |
| HORIZONTAL POSITION.THERE IS NO EXCEPTION IN THE |
| ACCESSIBILITY CODE ALLOWING GRAB BARS TO BE INSTALLED |
| IN A VERTICAL POSITION EVEN THOUGH THEY ARE NOT |
| "REQUIRED" GRAB BARS. |
| 6) SHT. P-601 - WATER HEATER SCHEDULE - IN THE "NOTES" |
| COLUMN REFERENCE IS MADE TO NUMBERED NOTES BUT THERE |
| ARE NO NUMBERED NOTES SHOWN. CLARIFY. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |