Plan Review Notes
Plan Review Notes For Permit 20020745
Permit Number 20020745
Review Stop P
Sequence Number 1
Notes
Date Text
2020-03-13 12:29:471) SHOW THE CLEAR INSIDE DIMENSIONS (L X W) FOR THE
 ACCESSIBLE TOILET STALLS AND TOILET ROOMS ON THE
 ENLARGED FLOOR PLANS. , WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHOW THE CLEAR FLOOR SPACE FOR THE HANDICAP
 ACCESSIBLE WATER CLOSETS ON THE ENLARGED FLOOR PLANS.
 COMPLY WITH 2017 FBC-ACCESS. SEC. 604.3. SHOW THE
 LENGTH AND WIDTH DIMENSIONS OF THE CLEAR FLOOR SPACE ON
 THE PLANS.
 3) SHT.A102 - WOMEN'S AND MEN'S RESTROOMS #115 & 116 -
 A LAVATORY IS REQUIRED IN THE ACCESSIBLE TOILET STALL
 PER 2017 FBC-ACCESS. SEC.604.8.1.6. SHOW THIS ON ALL
 APPLICABLE PLANS.
 4) SHT. A101 - THE TOILET ROOMS IN THE TENNIS CENTER
 ARE LABELED AS UNISEX.THE TOILET ROOMS SHALL BE LABELED
 AS GENDER SPECIFIC PER 2017 FBC-PLUMBING SEC.403.2.
 5) SHT. A401 - ALL GRAB BARS SHALL BE MEASURED FROM THE
 FINISH FLOOR TO THE TOP OF THE GRIPPING SURFACE PER
 2017 FBC-ACCESS. SEC.609.4.
 6) SHOW THE CLEAR INSIDE DIMENSIONS (L X W) OF ALL THE
 SHOWERS. WPB AMEND. TO FBC . SEC.107.2.1.
 7) SUBMIT AN ENLARGED FLOOR FLOOR PLAN FOR THE MEN'S
 TOILET ROOM IN THE RESTROOM FACILITY.WPB AMEND. TO FBC
 SEC. 107.2.1.
 8) A BACKFLOW PREVENTION DEVCE IS REQUIRED ON THE WATER
 SERVICE FOR THE TENNIS CENTER AND THE RESTROOM FACILITY
 PER THE CITY OF WEST PALM BEACH CROSS CONNECTION
 CONTROL MANUAL.. A SEPARATE PERMIT IS REQUIRED FOR THE
 BACKFLOW DEVICES.
 9) SUBMIT MANUFACTURER'S SPECIFICATIONS AND SHOP
 DRAWINGS FOR THE RAINWATER COLLECTION SYSTEM. WPB
 AMEND. TO FBC SEC. 107.2.1.
 10) NONPOTABLE WATER SYSTEMS SHALL BE IDENTIFIED IN
 ACCORDANCE WITH 2017 FBC-PLUMBING SECS.608.8 -
 608.8.2.3.
 11) SHT. P104 - DETAIL # 1- RESTROOM FACILITY - THE 3/4
 INCH CW LINES HAS A NOTE THAT READS" SEE 1/P101 FOR
 CONTINUATION". SHT. P101 IS FOR THE TENNIS CENTER AND
 THE LINE IS NOT SHOWN. CLARIFY.
 12) SHT. P104 - DETAIL #1 - THE WATER RISER SHOWS A 2
 INCH NPW BY FIXTURES P3, P7 & IM LINE TO NOWHERE.
 CLARIFY.
 13) SHT.P104 - THERE IS AN NPW LINE BY THE 1 1/2 NPW
 LINE TO P1A THAT HAS NO SIZE AND GOES NOWHERE. CLARIFY.
 14) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION MANUAL FOR THE FILTRATION SKID. WPB AMEND.
 TO FBC SEC. 107.2.1.
 15) BACK TO BACK WATER CLOSET CONNECTIONS SHALL COMPLY
 WITH 2017 FBC-PLUMBING SEC. 706.3 (EXCEPTION). SHOW
 COMPLIANCE ON PLANS.
 16) SHT. P105 - DETAIL #1 SHOWS SANITARY TEES USED IN
 THE HORIZONTAL POSITION WHICH IS NOT PERMITTED PER 2017
 FBC-PLUMBING TABLE 706.3. ALSO, THE PIPING TO FIXTURE
 P3 IS S- TRAPPED.
 17) SHT. P501 - THE T & P LINE FOR THE WATER HEATER
 SHALL DISCHARGE THROUGH AN AIR GAP LOCATED IN THE SAME
 ROOM AS THE WATER HEATER. 2017 FBC-PLUMBING SEC.504.6.
 18) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE
 WATTS ES-LSMMV-M1. DEVICES USED FOR TEMPERING WATER
 SHALL CONFORM TO ASSE 1070 PER 2017 FBC-PLUMBING SEC.
 607.1.2.
 19) AS OF APRIL 16, 2015 THE MINIMUM ENERGY FACTOR FOR
 THE 10 GALLON STORAGE WATER HEATER IS .95 PER 10 CFR
 430.32. THE ENERGY FACTOR FOR THE 66 GALLON STORAGE
 WATER HEATER SHALL BE 1.98. SHOW THESE CHANGES ON THE
 ENERGY CALCULATIONS.
 20) THE GRAB BARS IN THE ACCESSIBLE SHOWERS SHALL BE
 INSTALLED 6 INCHES MAXIMUM FROM ADJACENT WALLS. 2017
 FBC-ACCESS. SEC.608.3.2.
 21)THE CONTROLS IN THE ACCESSIBLE SHOWERS SHALL BE
 LOCATED 27 INCHES MAXIMUM FROM THE SEAT WALL. SHOW THIS
 ON THE FLOOR PLANS. 2017 FBC-ACCESS. SEC. 608.5.2.
 22) THE DOORS IN THE HANDICAP ACCESSIBLE TOILET STALLS
 SHALL BE LOCATED IN THE FRONT PARTITION OR IN THE SIDE
 WALL OR PARTITION FARTHEST FROM THE WATER CLOSET, NOT
 LOCATED DIRECTLY IN FRONT OF THE WATER CLOSET.. 2017
 FBC_ ACCESS. SEC.604.8.1.2.
 23) SHT. P104 - DETAIL #1 - THE 3/4 INCH NPW LINE IS
 ALSO NOTED AS "CW". CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW