2020-03-13 12:29:47 | 1) SHOW THE CLEAR INSIDE DIMENSIONS (L X W) FOR THE |
| ACCESSIBLE TOILET STALLS AND TOILET ROOMS ON THE |
| ENLARGED FLOOR PLANS. , WPB AMEND. TO FBC SEC. 107.2.1. |
| 2) SHOW THE CLEAR FLOOR SPACE FOR THE HANDICAP |
| ACCESSIBLE WATER CLOSETS ON THE ENLARGED FLOOR PLANS. |
| COMPLY WITH 2017 FBC-ACCESS. SEC. 604.3. SHOW THE |
| LENGTH AND WIDTH DIMENSIONS OF THE CLEAR FLOOR SPACE ON |
| THE PLANS. |
| 3) SHT.A102 - WOMEN'S AND MEN'S RESTROOMS #115 & 116 - |
| A LAVATORY IS REQUIRED IN THE ACCESSIBLE TOILET STALL |
| PER 2017 FBC-ACCESS. SEC.604.8.1.6. SHOW THIS ON ALL |
| APPLICABLE PLANS. |
| 4) SHT. A101 - THE TOILET ROOMS IN THE TENNIS CENTER |
| ARE LABELED AS UNISEX.THE TOILET ROOMS SHALL BE LABELED |
| AS GENDER SPECIFIC PER 2017 FBC-PLUMBING SEC.403.2. |
| 5) SHT. A401 - ALL GRAB BARS SHALL BE MEASURED FROM THE |
| FINISH FLOOR TO THE TOP OF THE GRIPPING SURFACE PER |
| 2017 FBC-ACCESS. SEC.609.4. |
| 6) SHOW THE CLEAR INSIDE DIMENSIONS (L X W) OF ALL THE |
| SHOWERS. WPB AMEND. TO FBC . SEC.107.2.1. |
| 7) SUBMIT AN ENLARGED FLOOR FLOOR PLAN FOR THE MEN'S |
| TOILET ROOM IN THE RESTROOM FACILITY.WPB AMEND. TO FBC |
| SEC. 107.2.1. |
| 8) A BACKFLOW PREVENTION DEVCE IS REQUIRED ON THE WATER |
| SERVICE FOR THE TENNIS CENTER AND THE RESTROOM FACILITY |
| PER THE CITY OF WEST PALM BEACH CROSS CONNECTION |
| CONTROL MANUAL.. A SEPARATE PERMIT IS REQUIRED FOR THE |
| BACKFLOW DEVICES. |
| 9) SUBMIT MANUFACTURER'S SPECIFICATIONS AND SHOP |
| DRAWINGS FOR THE RAINWATER COLLECTION SYSTEM. WPB |
| AMEND. TO FBC SEC. 107.2.1. |
| 10) NONPOTABLE WATER SYSTEMS SHALL BE IDENTIFIED IN |
| ACCORDANCE WITH 2017 FBC-PLUMBING SECS.608.8 - |
| 608.8.2.3. |
| 11) SHT. P104 - DETAIL # 1- RESTROOM FACILITY - THE 3/4 |
| INCH CW LINES HAS A NOTE THAT READS" SEE 1/P101 FOR |
| CONTINUATION". SHT. P101 IS FOR THE TENNIS CENTER AND |
| THE LINE IS NOT SHOWN. CLARIFY. |
| 12) SHT. P104 - DETAIL #1 - THE WATER RISER SHOWS A 2 |
| INCH NPW BY FIXTURES P3, P7 & IM LINE TO NOWHERE. |
| CLARIFY. |
| 13) SHT.P104 - THERE IS AN NPW LINE BY THE 1 1/2 NPW |
| LINE TO P1A THAT HAS NO SIZE AND GOES NOWHERE. CLARIFY. |
| 14) SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| INSTALLATION MANUAL FOR THE FILTRATION SKID. WPB AMEND. |
| TO FBC SEC. 107.2.1. |
| 15) BACK TO BACK WATER CLOSET CONNECTIONS SHALL COMPLY |
| WITH 2017 FBC-PLUMBING SEC. 706.3 (EXCEPTION). SHOW |
| COMPLIANCE ON PLANS. |
| 16) SHT. P105 - DETAIL #1 SHOWS SANITARY TEES USED IN |
| THE HORIZONTAL POSITION WHICH IS NOT PERMITTED PER 2017 |
| FBC-PLUMBING TABLE 706.3. ALSO, THE PIPING TO FIXTURE |
| P3 IS S- TRAPPED. |
| 17) SHT. P501 - THE T & P LINE FOR THE WATER HEATER |
| SHALL DISCHARGE THROUGH AN AIR GAP LOCATED IN THE SAME |
| ROOM AS THE WATER HEATER. 2017 FBC-PLUMBING SEC.504.6. |
| 18) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE |
| WATTS ES-LSMMV-M1. DEVICES USED FOR TEMPERING WATER |
| SHALL CONFORM TO ASSE 1070 PER 2017 FBC-PLUMBING SEC. |
| 607.1.2. |
| 19) AS OF APRIL 16, 2015 THE MINIMUM ENERGY FACTOR FOR |
| THE 10 GALLON STORAGE WATER HEATER IS .95 PER 10 CFR |
| 430.32. THE ENERGY FACTOR FOR THE 66 GALLON STORAGE |
| WATER HEATER SHALL BE 1.98. SHOW THESE CHANGES ON THE |
| ENERGY CALCULATIONS. |
| 20) THE GRAB BARS IN THE ACCESSIBLE SHOWERS SHALL BE |
| INSTALLED 6 INCHES MAXIMUM FROM ADJACENT WALLS. 2017 |
| FBC-ACCESS. SEC.608.3.2. |
| 21)THE CONTROLS IN THE ACCESSIBLE SHOWERS SHALL BE |
| LOCATED 27 INCHES MAXIMUM FROM THE SEAT WALL. SHOW THIS |
| ON THE FLOOR PLANS. 2017 FBC-ACCESS. SEC. 608.5.2. |
| 22) THE DOORS IN THE HANDICAP ACCESSIBLE TOILET STALLS |
| SHALL BE LOCATED IN THE FRONT PARTITION OR IN THE SIDE |
| WALL OR PARTITION FARTHEST FROM THE WATER CLOSET, NOT |
| LOCATED DIRECTLY IN FRONT OF THE WATER CLOSET.. 2017 |
| FBC_ ACCESS. SEC.604.8.1.2. |
| 23) SHT. P104 - DETAIL #1 - THE 3/4 INCH NPW LINE IS |
| ALSO NOTED AS "CW". CLARIFY. |
| |