Plan Review Notes
Plan Review Notes For Permit 20020745
Permit Number 20020745
Review Stop M
Sequence Number 1
Notes
Date Text
2020-03-11 15:35:101ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20020745
 3/11/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-101: AIR HANDLERS ARE NOT ALLOWED IN THE
 ATTICS OF COMMERCIAL BUILDINGS- SECTION C403.2.9.6 FBC
 EC. THE UNITS WILL HAVE TO BE RELOCATED.
  
 2 )M-101: PLEASE NOTE THAT AUTOMATIC SHUTOFF DAMPERS,
 EITHER MOTORIZED OR GRAVITY, WILL BE REQUIRED FOR THE
 O/A INTAKES TO THE RELOCATED AIR HANDLERS- SECTION
 C403.2.4.3 FBC EC.
  
 3) M-101: PROVIDE A DUCT SMOKE DETECTOR IN THE SUPPLY
 SYSTEM OF AHU-2 PER SECTION 606.2.1 FBC M. PLEASE NOTE
 THAT AN EXEMPTION CAN BE APPLIED IF THE MANUFACTURER'S
 PERFORMANCE DATA INDICATES THE AIR HANDLER IS NOT
 CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR.
  
 4) SUBMIT AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW SYSTEMS- SECTION C403.2.1 FBC EC.
  
 5) SUBMIT AN ENERGY COMPLIANCE REPORT FOR THE NEW
 TENNIS CENTER- SEE SECTIONS C101.5 AND C401.2 FBC EC
 FOR COMPLIANCE AND SUBMITTAL INFORMATION.
  
 6) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3.1.1 FBC ML. PROVIDE A
 SCHEDULE ON THE PLAN THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 7) PROVIDE A CONDENSATE DISPOSAL PLAN- SECTION 307.2.1
 FBC M.
  
 8) PROVIDE ENGINEERING FOR INSTALLATION OF THE
 CONDENSER PAD AND MOUNTING OF THE CONDENSERS- SECTION
 301.15 FBC M.
  
 9) A-152 & A-203: A) A MINIMUM 30 INCHES DEEP AND 30
 INCHES WIDE LEVEL PLATFORM WITH 42" HIGH GUARD RAILS
 SHALL BE PROVIDED FOR SERVICE AND REPLACEMENT OF THE
 ROOFTOP EXHAUST FANS- SECTION 306.5.1 FBC M. B) A
 RECEPTACLE OUTLET SAHLL BE POVIDED AT OR NEAR THE FANS
 IN ACCORDANCE WITH NFPA 70- SECTION 306.5.2 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  
  
  