Plan Review Notes
Plan Review Notes For Permit 20020745
Permit Number 20020745
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-03-06 11:57:07THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEET G 101 - THE OCCUPANCY LOAD CALCULATION FOR THE
 CONFERENECE ROOM IS INDICATED AS B 100/3. THIS
 CONFERENCE ROOM IS AN ASSEMBLY SPACE PER THE FL FIRE
 PREVENTION CODE.
  
 THE OCCUPANCY LOAD SHOULD BE 20, WITH AN A REPLACE THE
 B DESIGNATION.
  
 PLEASE REVIEW AND REVISE AT THE APPLICABLE TIME PRIOR
 TO CO
  
  
  
 2) SHEET G 101 - THE OCCUPANCY LOAD CALCULATION FOR THE
 LARGE OPEN CONFERENECE SPACE IS INDICATED A B WHERE IT
 SHOULD BE A.
  
 PLEASE REVIEW AND REVISE AT THE APPLICABLE TIME PRIOR
 TO CO
  
  
  