Plan Review Notes For Permit 20020745 |
Permit Number |
20020745 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-03-17 12:59:37 | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | 1) NEED TO SUBMIT AN AIC CALCULATION FOR THE SERVICE | | 110.24 | | | | 2) OUTLET(S) FOR WATER FOUNTAIN TO BE ACCESSIBLE IF | | THEY ARE OF THE GCFI TYPE. 422.52, 422.5 | | | | 3) NEED A LOAD CALCULATION PER 220, 215.5 | | | | 4) LOW VOLTAGE, SITE LIGHTING, FIRE ALARM, AND SOLAR | | SYSTEMS ALL REQUIRE SEPARATE PERMITS. |
|