2020-03-13 17:01:40 | BUILDING REVIEW COMMENTS: |
| |
| W.P.B. PERMIT: 20020745 |
| REVIEWED: MARCH 13, 2020 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER PX4191 |
| [email protected] |
| 561-805-6718 |
| |
| FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK |
| BELOW) |
| HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ |
| BUILDING-PERMIT-FORMS |
| FBC[B] = FBC BUILDING |
| FBC[A] = FBC ACCESSIBILITY |
| FBC[E] = FBC ENERGY CONSERVATION |
| |
| 1) 1004 FBC[B]SHEET G-101 (MAIN BUILDING) |
| PLEASE BASE OCCUPANCY UPON THE INTENDED USE. 15 SQ. FT. |
| PER OCCUPANT IS FOR TABLES AND CHAIRS. THE PLAN IS |
| SHOWN WITH CHAIRS ONLY AND THERE ARE 85 CHAIRS |
| REPRESENTED. CONCENTATED CHAIRS USES 7 SQ. FT. PER |
| OCCUPANT. SINCE THIS SPACE WILL BE USED FOR A VARIETY |
| OF ASSEMBLY AND YOU ARE DEVIATING FROM CODE WORST CASE, |
| PLEASE CONTACT THE FIRE MARSHALL AND BUILDING OFFICIAL |
| TO DISCUSS. |
| [email protected] (FIRE MARSHALL) AND [email protected] |
| (BUILDING OFFICIAL) |
| SHOW CLEAR PATH OF EGRESS OR SHOW DIMENSION BETWEEN |
| CHAIRS AND WALL SINCE IT APPEARS LESS THAN 36 INCHES. |
| |
| 2) 1004 FBC[B]ADJUST THE TAG MAIN INTERIO ASSEMBLY. IT |
| SHOWS B AND USES 15 FOR COME UP WITH 59 OCCUPANTS. |
| PLEASE UPDATE TO A-3 AND USE OCCUPANT FACTOR BASED ON |
| USE OF THE SPACE. |
| |
| 3) 1004 FBC[B] SHEET G-10 (RESTROOM FACILITY) |
| LOCKER ROOMS ARE USING BUSINESS OCCUPANCY AT 100 SQ. |
| FT. PER, BUT THERE IS A 50 GROSS FOR LOCKER ROOMS |
| STATED IN TABLE 1004.1.2 |
| ALSO, BUSINESS IS USED FOR MAIN RESTROOM AREA. THESE |
| DON?T SUPPORT BUSINESS USES. PLEASE USE OCCUPANCY COUNT |
| AT LEAST MINIMUM OF FIXTURES SINCE THEY COULD BE USED |
| SIMULTANEOUSLY. |
| |
| 4) 401.2 FBC[CE] APPLICATION. COMMERCIAL BUILDINGS |
| SHALL COMPLY WITH ONE OF THE FOLLOWING: |
| 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1, |
| EXCLUDING SECTION 9.4.1.1(G) OF THE STANDARD. |
| 2. THE REQUIREMENTS OF SECTIONS C402 THROUGH C405. IN |
| ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY WITH |
| SECTION C406 AND TENANT SPACES SHALL COMPLY WITH |
| SECTION C406.1.1. |
| 3. THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404, |
| C405.2, C405.3, C405.5, C405.6 AND C407. THE BUILDING |
| ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 PERCENT |
| OF THE STANDARD REFERENCE DESIGN BUILDING. |
| - PLEASE PROVIDE DOCUMENTATION FOR COMPLIANCE WITH THE |
| ENERGY CODE FOR EACH BUILDING. |
| |
| 5) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR |
| WINDOWS, WINDOW MULL AND TRANSOM, OR INDICATE THAT THIS |
| WILL BE A DEFERRED SUBMITTAL. |
| |
| 6) 107.2.1.2 FBC[AMENDED] PROVIDE STAIRCASE AND GUARD |
| RAIL ENGINEERING, OR INDICATE THAT IT WILL BE DEFERRED |
| SUBMITTAL. |
| |
| 7) 1507.4.2 FBC[B] DECK SLOPE. MINIMUM SLOPES FOR METAL |
| ROOF PANELS SHALL COMPLY WITH THE FOLLOWING: |
| A. THE MINIMUM SLOPE FOR LAPPED, NONSOLDERED SEAM METAL |
| ROOF PANELS WITHOUT APPLIED LAP SEALANT SHALL BE THREE |
| UNITS VERTICAL IN 12 UNITS HORIZONTAL (25-PERCENT |
| SLOPE). |
| B. THE MINIMUM SLOPE FOR LAPPED, NONSOLDERED SEAM METAL |
| ROOF PANELS WITH APPLIED LAP SEALANT SHALL BE ONE-HALF |
| UNIT VERTICAL IN 12 UNITS HORIZONTAL (4-PERCENT SLOPE). |
| LAP SEALANTS SHALL BE APPLIED IN ACCORDANCE WITH THE |
| APPROVED MANUFACTURER?S INSTALLATION INSTRUCTIONS. |
| B. THE MINIMUM SLOPE FOR STANDING-SEAM METAL ROOF PANEL |
| SYSTEMS SHALL BE ONE-QUARTER UNIT VERTICAL IN 12 UNITS |
| HORIZONTAL (2-PERCENT SLOPE). |
| -PLEASE PROVIDE PRODUCT APPROVALS FOE METAL ROOFING |
| THAT MEET 1507.4.2, OR INDICATE THAT THIS WILL BE A |
| DEFERRED SUBMITTAL. |
| |
| 8) 107.3.4.1 FBC[AMENDED] SUBMIT TRUSS SHOP DRAWINGS TO |
| THE BUILDING INSPECTOR PRIOR TO INSTALLATION. |
| - THE TRUSS SUBMITTAL CAN BE APPROVED NOW IF PUT IN |
| SUPPORTING DOCUMENTS AS A SUBMITTAL, OR IT CAN BE |
| DEFERRED. IF DEFERED THE TRUSS PACKAGE NEEDS TO BE |
| REVIEWED BY BUILDING INSPECTOR PRIOR TO INSTALLATION. |
| |
| 9) 803.4 FBC[A] BENCHES. A BENCH COMPLYING WITH 903 |
| SHALL BE PROVIDED WITHIN THE ROOM. |
| |
| 10) 903.4 FBC[A] BACK SUPPORT. THE BENCH SHALL PROVIDE |
| FOR BACK SUPPORT OR SHALL BE AFFIXED TO A WALL. BACK |
| SUPPORT SHALL BE 42 INCHES LONG MINIMUM AND SHALL |
| EXTEND FROM A POINT 2 INCHES MAXIMUM ABOVE THE SEAT |
| SURFACE TO A POINT 18 INCHES MINIMUM ABOVE THE SEAT |
| SURFACE. BACK SUPPORT SHALL BE 21/2 INCHES MAXIMUM FROM |
| THE REAR EDGE OF THE SEAT MEASURED HORIZONTALLY. |
| |
| NOTES: |
| |
| PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| EACH COMMENT IS BEING ADDRESSED. |
| |
| FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F 8-5) TO |
| DISCUSS COMMENTS, OR E-MAIL ANYTIME [email protected] |
| |
| |
| |