2020-03-13 17:01:40BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 20020745
 REVIEWED: MARCH 13, 2020
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 1) 1004 FBC[B]SHEET G-101 (MAIN BUILDING)
 PLEASE BASE OCCUPANCY UPON THE INTENDED USE. 15 SQ. FT.
 PER OCCUPANT IS FOR TABLES AND CHAIRS. THE PLAN IS
 SHOWN WITH CHAIRS ONLY AND THERE ARE 85 CHAIRS
 REPRESENTED. CONCENTATED CHAIRS USES 7 SQ. FT. PER
 OCCUPANT. SINCE THIS SPACE WILL BE USED FOR A VARIETY
 OF ASSEMBLY AND YOU ARE DEVIATING FROM CODE WORST CASE,
 PLEASE CONTACT THE FIRE MARSHALL AND BUILDING OFFICIAL
 TO DISCUSS.
 [email protected] (FIRE MARSHALL) AND [email protected]
 (BUILDING OFFICIAL)
 SHOW CLEAR PATH OF EGRESS OR SHOW DIMENSION BETWEEN
 CHAIRS AND WALL SINCE IT APPEARS LESS THAN 36 INCHES.
  
 2) 1004 FBC[B]ADJUST THE TAG MAIN INTERIO ASSEMBLY. IT
 SHOWS B AND USES 15 FOR COME UP WITH 59 OCCUPANTS.
 PLEASE UPDATE TO A-3 AND USE OCCUPANT FACTOR BASED ON
 USE OF THE SPACE.
  
 3) 1004 FBC[B] SHEET G-10 (RESTROOM FACILITY)
 LOCKER ROOMS ARE USING BUSINESS OCCUPANCY AT 100 SQ.
 FT. PER, BUT THERE IS A 50 GROSS FOR LOCKER ROOMS
 STATED IN TABLE 1004.1.2
 ALSO, BUSINESS IS USED FOR MAIN RESTROOM AREA. THESE
 DON?T SUPPORT BUSINESS USES. PLEASE USE OCCUPANCY COUNT
 AT LEAST MINIMUM OF FIXTURES SINCE THEY COULD BE USED
 SIMULTANEOUSLY.
  
 4) 401.2 FBC[CE] APPLICATION. COMMERCIAL BUILDINGS
 SHALL COMPLY WITH ONE OF THE FOLLOWING:
 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1,
 EXCLUDING SECTION 9.4.1.1(G) OF THE STANDARD.
 2. THE REQUIREMENTS OF SECTIONS C402 THROUGH C405. IN
 ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY WITH
 SECTION C406 AND TENANT SPACES SHALL COMPLY WITH
 SECTION C406.1.1.
 3. THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404,
 C405.2, C405.3, C405.5, C405.6 AND C407. THE BUILDING
 ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 PERCENT
 OF THE STANDARD REFERENCE DESIGN BUILDING.
 - PLEASE PROVIDE DOCUMENTATION FOR COMPLIANCE WITH THE
 ENERGY CODE FOR EACH BUILDING.
  
 5) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR
 WINDOWS, WINDOW MULL AND TRANSOM, OR INDICATE THAT THIS
 WILL BE A DEFERRED SUBMITTAL.
  
 6) 107.2.1.2 FBC[AMENDED] PROVIDE STAIRCASE AND GUARD
 RAIL ENGINEERING, OR INDICATE THAT IT WILL BE DEFERRED
 SUBMITTAL.
  
 7) 1507.4.2 FBC[B] DECK SLOPE. MINIMUM SLOPES FOR METAL
 ROOF PANELS SHALL COMPLY WITH THE FOLLOWING:
 A. THE MINIMUM SLOPE FOR LAPPED, NONSOLDERED SEAM METAL
 ROOF PANELS WITHOUT APPLIED LAP SEALANT SHALL BE THREE
 UNITS VERTICAL IN 12 UNITS HORIZONTAL (25-PERCENT
 SLOPE).
 B. THE MINIMUM SLOPE FOR LAPPED, NONSOLDERED SEAM METAL
 ROOF PANELS WITH APPLIED LAP SEALANT SHALL BE ONE-HALF
 UNIT VERTICAL IN 12 UNITS HORIZONTAL (4-PERCENT SLOPE).
 LAP SEALANTS SHALL BE APPLIED IN ACCORDANCE WITH THE
 APPROVED MANUFACTURER?S INSTALLATION INSTRUCTIONS.
 B. THE MINIMUM SLOPE FOR STANDING-SEAM METAL ROOF PANEL
 SYSTEMS SHALL BE ONE-QUARTER UNIT VERTICAL IN 12 UNITS
 HORIZONTAL (2-PERCENT SLOPE).
 -PLEASE PROVIDE PRODUCT APPROVALS FOE METAL ROOFING
 THAT MEET 1507.4.2, OR INDICATE THAT THIS WILL BE A
 DEFERRED SUBMITTAL.
  
 8) 107.3.4.1 FBC[AMENDED] SUBMIT TRUSS SHOP DRAWINGS TO
 THE BUILDING INSPECTOR PRIOR TO INSTALLATION.
 - THE TRUSS SUBMITTAL CAN BE APPROVED NOW IF PUT IN
 SUPPORTING DOCUMENTS AS A SUBMITTAL, OR IT CAN BE
 DEFERRED. IF DEFERED THE TRUSS PACKAGE NEEDS TO BE
 REVIEWED BY BUILDING INSPECTOR PRIOR TO INSTALLATION.
  
 9) 803.4 FBC[A] BENCHES. A BENCH COMPLYING WITH 903
 SHALL BE PROVIDED WITHIN THE ROOM.
  
 10) 903.4 FBC[A] BACK SUPPORT. THE BENCH SHALL PROVIDE
 FOR BACK SUPPORT OR SHALL BE AFFIXED TO A WALL. BACK
 SUPPORT SHALL BE 42 INCHES LONG MINIMUM AND SHALL
 EXTEND FROM A POINT 2 INCHES MAXIMUM ABOVE THE SEAT
 SURFACE TO A POINT 18 INCHES MINIMUM ABOVE THE SEAT
 SURFACE. BACK SUPPORT SHALL BE 21/2 INCHES MAXIMUM FROM
 THE REAR EDGE OF THE SEAT MEASURED HORIZONTALLY.
  
 NOTES:
  
 PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F 8-5) TO
 DISCUSS COMMENTS, OR E-MAIL ANYTIME [email protected]
  
  
  