2020-02-21 12:30:17 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #20020708 |
| 2/21/20 |
| |
| CODES IN EFFECT: |
| |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE ARCHITECT OF RECORD JAMES C. PAINE JR. SHALL |
| PROVIDE HIS RAISED OR INK SEAL AND WET SIGNATURE ON THE |
| PLAN-- FL STATUTE 481.221 AND SECTION 61G-16.005 |
| FLORIDA ADMINISTRATIVE CODE. |
| |
| 2) REMOVE THE PLUMBING DETAILS AND NOTES FROM THE PLAN |
| THAT DO NOT PERTAIN TO THIS AC PROJECT- SECTION 107.2.1 |
| WPB. |
| |
| 3) PROVIDE AN AHRI CERTIFCATE FOR THE AC-2 SYSTEM- |
| SECTION R501.7 FBC EC.( I WAS UNABLE TO VERIFY AHRI |
| CERTIFICATION USING THE REFERENCE NUMBER THAT IS LISTED |
| IN THE EQUIPMENT SCHEDULE). |
| |
| 4) PROVIDE THE RETURN TRANSFER DUCT SIZE FOR THE |
| DEN/OFFICE- SECTION M1602.3 FBC RES. |
| |
| 5) PROVIDE CONDENSATE DISPOSAL DETAILS FOR THE NEW AIR |
| HANDLERS- SECTION M1411.3 FBC RES. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |