2020-06-22 14:49:08 | 3RD REVIEW FBC-2017 MECHANICAL |
| PERMIT-20020673 |
| |
| CODES IN EFFECT: |
| |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| PLEASE SEE 3RD REVIEW COMMENT BELOW: |
| |
| |
| 1) SHEET M4.6: THE REVISED SHEET SHOWS UNDERSLAB |
| REFRIGERANT PIPING RUNS CROSSING THE INDIVIDUAL |
| PROPERTY LINES OF THE TOWNHOUSES. PLEASE SEE SECTION |
| R302.2 FBC RES AND RELOCATE THE CONDENSERS BACK TO |
| THEIR ORIGINAL LOCATIONS AT THE REAR OF EACH TOWNHOUSE. |
| |
| 2) THE CONTRACTOR OR QUALIFIER OF RECORD WHO PREPARED |
| THE MECHANICAL DRAWINGS SHALL PROVIDE HIS/HER SIGNATURE |
| ON EACH PLAN SHEET- SECTION 107.2.1 WPB. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| |