2020-05-08 14:39:152ND REVIEW FBC-2017 MECHANICAL
 PERMIT #20020670
 5/8/20
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED
  
 1) SHEETS M1 & M2: THE MECHANICAL PLANS ARE OLDER
 VERSIONS AND SHOULD BE UPDATED TO MATCH THE OTHER NEW
 PLANS FOR THE MODELS- SECTION 107.2.1 WPB. PLEASE NOTE
 THE CONDENSER LOCATIONS AT THE REAR OF EACH TOWNHOUSE
 AS SHOWN ON SHEET M4.6 SHOWING ARE APPROVED LOCATIONS.
  
 2) SHEET M1, NAVARRE MODEL:
 A) IT APPEARS THAT FLEX DUCTS WILL BE INSTALLED IN THE
 GARAGE. PLEASE PLACE A NOTE TO VERIFY THE DUCTS WILL BE
 INSTALLED ABOVE THE REQUIRED DRYWALL CEILING- SECTION
 R302.5.2 FBC RES
 B) THE MAIN RETURN TO THE AC CLOSET IS SLIGHTLY
 UNDERSIZED- 50 SQ. INCHES PER 100 CFMS REQUIRED. A
 24X24 GRILL WILL BE ADEQUATE.
  
 3) REVISE THE SURVEY TO SHOW CORRECT TOWNHOUSE AND LOT
 LOCATIONS- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY,
  