Plan Review Notes
Plan Review Notes For Permit 20020648
Permit Number 20020648
Review Stop M
Sequence Number 2
Notes
Date Text
2020-05-08 12:50:41 
 2ND REVIEW FBC-2017 MECHANICAL
 PERMIT #20020648
 5/8/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M4.6: THE REVISED SHEET SHOWS UNDERSLAB
 REFRIGERANT PIPING RUNS CROSSING THE INDIVIDUAL
 PROPERTY LINES OF THE TOWNHOUSES. PLEASE SEE SECTION
 R302.2 FBC RES AND RELOCATE THE CONDENSERS BACK TO
 THEIR ORIGINAL LOCATIONS AT THE REAR OF EACH TOWNHOUSE.
  
 2) THE 421 18TH ST. ADDRESS ON THE AC CALCULATIONS DOES
 NOT MATCH THE ADDRESSES ON THE PERMIT APPLICATION AND
 THE ENERGY CALCS. PLEASE PROVIDE CALCULATIONS
 SPECIFICALLY FOR THE PROPOSED TOWNHOUSE- SECTION
 R403.7.1 FBC EC. REVISE THE SURVEY TO SHOW CORRECT
 TOWNHOUSE AND LOT LOCATIONS- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  