2021-02-22 07:19:40 | SHEET M4.6 IS STILL SHOWING THE REFRIGERATE LINES | | RUNNING UNDER SLAB TO THE SIDE OF THE BUILDING. THE | | REFRIGERATE LINES CANNOT RUN UNDER THE SLAB UNDER | | OTHERS PROPERTY. PLEASE SHOW THE CONDENSING UNIT FOR | | EACH TOWNHOME AT THE REAR OF THE BUILDING AND BETWEEN | | THE PROPERTY LINES OF ITS OWN PROPERTY. FBC RES R302.2 | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|