Plan Review Notes For Permit 20020613 |
Permit Number |
20020613 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-02-19 13:30:05 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) SHEET FA 2 - OFFICE 3 DOES NOT INDICATE ANY | | NOTIFICATION DEVICE PER NFPA 101 & 72 | | | | PER NFPA 101, CH 9 | | | | 9.6.3.5 UNLESS OTHERWISE PROVIDED IN 9.6.3.5.1 THROUGH | | 9.6.3.5.8, | | NOTIFICATION SIGNALS FOR OCCUPANTS TO EVACUATE SHALL BE | | AUDIBLE, AND | | VISIBLE SIGNALS IN ACCORDANCE WITH NFPA 72, NATIONAL | | FIRE ALARM | | AND SIGNALING CODE. AND ICC/ANSI A117.1, AMERICAN | | NATIONAL | | STANDARD FOR ACCESSIBLE AND USABLE BUILDINGS AND | | FACILITIES, OR | | OTHER MEANS OF NOTIFICATION ACCEPTABLE TO THE AUTHORITY | | HAVING | | JURISDICTION SHALL BE PROVIDED. | | | | 9.6.3.5.1 AREAS NOT SUBJECT TO OCCUPANCY BY PERSONS WHO | | ARE | | HEARING IMPAIRED SHALL NOT BE REQUIRED TO COMPLY WITH | | THE | | PROVISIONS FOR VISIBLE SIGNALS | | | | PLEASE REVIEW AND CORRECT AND/OR JUSTIFY WITH SPECIFIC | | CODE REFERENCES. | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | |
|