2020-02-24 06:07:30 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND |
| SIGNED/SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY THE |
| ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS |
| 471.003(2)(H); 471.025; WPB FBC 107.1 |
| |
| 2. VALUE LOW FOR AMOUNT OF WORK SHOWN. |
| |
| CITY ORDINANCE AND FBC 109.3 BUILDING PERMIT |
| VALUATIONS. IF, IN THE OPINION OF THE BUILDING |
| OFFICIAL, THE CLAIMED VALUATION OF BUILDING, |
| ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR |
| PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE |
| APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS THE |
| APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR |
| BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO |
| MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR |
| PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS |
| SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| |
| 3. EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER |
| CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR OUT-LINE |
| LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN EXTERNALLY |
| OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL |
| UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN NEC |
| 600.6(A)(1) |
| |
| 4. ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 405.1 |
| SHALL HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT |
| OR WHEN NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & |
| TIME CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME |
| SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMING |
| DURING A LOSS OF POWER FOR A MINIMUM OF 10 HOURS. |
| FBC-EC 405.2.5. PROVIDE COMPLIANCE |
| |
| 5. SEPARATE ELECTRICAL PERMIT FOR NEW 120V CIRCUIT TO |
| MONUMENT SIGN REQUIRED BY LICENSED ELECTRICIAN. |
| REFERENCE PERMIT NUMBER OF SEPARATE ELECTRICAL PERMIT |
| WHEN RESUBMITTING TO SHOW COMPLIANCE. FBC 105.1, FBC |
| 107.2.1, F.S. 489.505 (#19) AND F.A.C. 61G6-7.001 |
| SPECIALTY ELECTRICAL CONTRACTORS (#2 SIGN SPECIALTY |
| CONTRACTOR) |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A |
| COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS |
| |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |