Plan Review Notes
Plan Review Notes For Permit 20020563
Permit Number 20020563
Review Stop B
Sequence Number 1
Notes
Date Text
2020-03-20 11:50:11SHUTTERS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) ATTACHMENT SPACING SHOWN FOR THE CONCRETE BLOCK ON
 THE "SCHEDULE FOR INSTALLATION OF OPENING PROTECTIVE
 DEVICES OR ASSEMBLIES" DOES NOT MEET THE ATTACHMENT
 SPACING SHOWN ON THE PRODUCT APPROVAL. PLEASE CIRCLE
 THE SPACING REQUIREMENTS ON THE PRODUCT APPROVAL FOR
 BETTER CLARITY FOR PLAN REVIEW. PLEASE REVIEW THE
 ATTACHMENT SPACING AND REVISE THE "SCHEDULE FOR
 INSTALLATION OF OPENING PROTECTIVE DEVICES OR
 ASSEMBLIES" FORM.
 2) PLEASE PROVIDE THE FRONT PAGES OF THE PRODUCT
 APPROVAL. ( FLORIDA PRODUCT APPROVAL FRONT PAGE.)
  