Plan Review Notes
Plan Review Notes For Permit 20020505
Permit Number 20020505
Review Stop G
Sequence Number 1
Notes
Date Text
2020-02-25 17:16:3802/25/2020 1ST GAS REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE PROVIDE A VALID LP LICENSE FOR A CONTRACTOR
 OF THE WORK BEING DONE AND PULL A SUB PERMIT FOR THE
 WORK BEING DONE PER THE 2017 FBC WPB A 105.1.
  
 2. GAS RISER DIAGRAM REQUIRED WPB AMENDMENTS TO THE FBC
 SEC. 107.3.5.3 (12) RESIDENTIAL GAS.
  
 3. ON THE GAS ISOMETRIC DRAWING CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC RES.
 SECS. G2413.4.1, G2413.4.2.
  
 4. SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE
 DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR
 ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM PER THE 2017 FBC RES. SEC. G2413.3.
  
 5. PLEASE SHOW TYPE OF GAS (LP OR NATURAL) PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 6. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC
 RES. SEC. G2413.4.1.
  
 7. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE AND UNION SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR PER THE 2017 FBC
 RES. SEC. G2420.4.
  
 8. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF
 THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH
 FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA
 STATUTE 471. WPB AMENDMENTS TO THE FBC SEC. 107.1
 GENERAL.
  
 9. PLEASE PROVIDE REGULATOR SPECS AND AS INSTALLED
 OUTDOORS IT SHALL BE DESIGNED TO BE PROTECTED SO THEIR
 OPERATION WILL NOT BE AFFECTED BY THE ELEMENTS. PROVIDE
 DOCUMENTATION FROM THE MANUFACTURER THAT THE REGULATORS
 ARE APPROVED FOR EXTERIOR USE. NFPA 58-11 SEC. 6.8.1.5.
  
 10. CLEARLY SHOW THE DISTANCE OF THE TANK FROM THE
 EXTERIOR ADJACENT PROPERTY LINES AND DRIVEWAY, THE
 DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION,
 OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY
 BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK
 PER NFPA 58, TABLE 3-2.2.2.
  
 11. PLEASE PROVIDE HOW YOU ARE GOING TO PROTECT THIS
 TANK COVER FROM VEHICULAR TRAFFIC OR PARKING ABOVE IT
 ON GRASS
  
 12. IT IS INDICATED THE TANK IS BELOW THE GROUND, BUT
 SHOW THE METHOD OF REQUIRED PROTECTION FOR THE LP TANK
 AND APPURTENANCES PER NFPA 58, IT SHALL BE ANCHORED PER
 NFPA 58 SEC.3-2.2.7 (H) PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 13. CLEARLY INDICATE ON THE TIE-DOWN SHEET IF THE LP
 TANK TIE-DOWN METHOD AND IF YOU ARE USING STRAPS OR
 CABLE, IF CABLE HOW IS IT PROTECTED FOR THE LP TANK AND
 APPURTENANCES PER NFPA 58. WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 14. PROVIDE THE SIZE OF THE HOLD-DOWN CABLES/STRAPS FOR
 THE TANK AND THE TYPE AND LENGTH OF GROUND ANCHORS TO
 BE INSTALLED TO PREVENT FLOTATION. NFPA 58 SEC.
 6.6.1.6.
  
 15. A CATHODIC PROTECTION SYSTEM SHALL BE REQUIRED PER
 NFPA 58 SECS. 5.2.1.11, 6.6.6.1 (I) AND SHALL BE
 MONITORED PER NFPA 58 SEC.6.6.6.1 (J). SUBMIT DETAILS
 ON THE TYPE OF CATHODIC PROTECTION, SIZE (LBS.) & A
 NUMBER OF MAGNESIUM BAG(S), SIZE & TYPE OF ANODE CABLE
 AMOUNT OF WATER TO ACTIVATE IT.
  
 16. SHOW THE DEPTH OF THE CONTAINER BELOW GRADE. COMPLY
 WITH NFPA 58 SEC. 6.6.6.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  