2020-02-25 17:16:38 | 02/25/2020 1ST GAS REVIEW **DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. PLEASE PROVIDE A VALID LP LICENSE FOR A CONTRACTOR |
| OF THE WORK BEING DONE AND PULL A SUB PERMIT FOR THE |
| WORK BEING DONE PER THE 2017 FBC WPB A 105.1. |
| |
| 2. GAS RISER DIAGRAM REQUIRED WPB AMENDMENTS TO THE FBC |
| SEC. 107.3.5.3 (12) RESIDENTIAL GAS. |
| |
| 3. ON THE GAS ISOMETRIC DRAWING CLEARLY SHOWS THE |
| LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC RES. |
| SECS. G2413.4.1, G2413.4.2. |
| |
| 4. SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE |
| DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS |
| OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR |
| ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS |
| SYSTEM PER THE 2017 FBC RES. SEC. G2413.3. |
| |
| 5. PLEASE SHOW TYPE OF GAS (LP OR NATURAL) PER THE WPB |
| AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| 6. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC |
| RES. SEC. G2413.4.1. |
| |
| 7. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| A LISTED SHUTOFF VALVE AND UNION SHALL BE INSTALLED |
| IMMEDIATELY AHEAD OF EACH MP REGULATOR PER THE 2017 FBC |
| RES. SEC. G2420.4. |
| |
| 8. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF |
| THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH |
| FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA |
| STATUTE 471. WPB AMENDMENTS TO THE FBC SEC. 107.1 |
| GENERAL. |
| |
| 9. PLEASE PROVIDE REGULATOR SPECS AND AS INSTALLED |
| OUTDOORS IT SHALL BE DESIGNED TO BE PROTECTED SO THEIR |
| OPERATION WILL NOT BE AFFECTED BY THE ELEMENTS. PROVIDE |
| DOCUMENTATION FROM THE MANUFACTURER THAT THE REGULATORS |
| ARE APPROVED FOR EXTERIOR USE. NFPA 58-11 SEC. 6.8.1.5. |
| |
| 10. CLEARLY SHOW THE DISTANCE OF THE TANK FROM THE |
| EXTERIOR ADJACENT PROPERTY LINES AND DRIVEWAY, THE |
| DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION, |
| OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY |
| BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK |
| PER NFPA 58, TABLE 3-2.2.2. |
| |
| 11. PLEASE PROVIDE HOW YOU ARE GOING TO PROTECT THIS |
| TANK COVER FROM VEHICULAR TRAFFIC OR PARKING ABOVE IT |
| ON GRASS |
| |
| 12. IT IS INDICATED THE TANK IS BELOW THE GROUND, BUT |
| SHOW THE METHOD OF REQUIRED PROTECTION FOR THE LP TANK |
| AND APPURTENANCES PER NFPA 58, IT SHALL BE ANCHORED PER |
| NFPA 58 SEC.3-2.2.7 (H) PER THE WPB AMENDMENTS TO THE |
| FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 13. CLEARLY INDICATE ON THE TIE-DOWN SHEET IF THE LP |
| TANK TIE-DOWN METHOD AND IF YOU ARE USING STRAPS OR |
| CABLE, IF CABLE HOW IS IT PROTECTED FOR THE LP TANK AND |
| APPURTENANCES PER NFPA 58. WPB AMENDMENTS TO THE FBC |
| SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 14. PROVIDE THE SIZE OF THE HOLD-DOWN CABLES/STRAPS FOR |
| THE TANK AND THE TYPE AND LENGTH OF GROUND ANCHORS TO |
| BE INSTALLED TO PREVENT FLOTATION. NFPA 58 SEC. |
| 6.6.1.6. |
| |
| 15. A CATHODIC PROTECTION SYSTEM SHALL BE REQUIRED PER |
| NFPA 58 SECS. 5.2.1.11, 6.6.6.1 (I) AND SHALL BE |
| MONITORED PER NFPA 58 SEC.6.6.6.1 (J). SUBMIT DETAILS |
| ON THE TYPE OF CATHODIC PROTECTION, SIZE (LBS.) & A |
| NUMBER OF MAGNESIUM BAG(S), SIZE & TYPE OF ANODE CABLE |
| AMOUNT OF WATER TO ACTIVATE IT. |
| |
| 16. SHOW THE DEPTH OF THE CONTAINER BELOW GRADE. COMPLY |
| WITH NFPA 58 SEC. 6.6.6.1. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |