2020-02-25 10:51:19 | ***CORRECTIONS*** |
| PETER E VALENTI |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6673 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| FBC M = FBC MECHANICAL |
| |
| BUILDING REVIEW DENIED: |
| |
| 1) FBC B 107.2.1, THE COVER PAGE CLASSIFIES THE |
| OCCUPANCY AS R-2. THIS NEEDS TO BE CHANGED TO R-3. |
| |
| 2) FBC R 310.2.1, PAGE 4.0 EGRESS WINDOW DETAIL SHOWS A |
| MINIMUM CLEAR HEIGHT OF 22". THIS NEEDS TO BE CHANGED |
| TO 24". |
| |
| 3) FBC B 107.2.1, PAGES 9.0, 10.0, & 11.0 DO NOT |
| IDENTIFY THE LOCATION OF BATHROOM DOOR/ENTRY. PLEASE |
| SHOW ON PLANS. |
| |
| 4) FBC R FIGURE R 301.2(7), ON PAGES 3.0 AND 8.0, THE |
| WIND LOAD SCHEDULE ZONES FOR ROOF AND WALLS DO NOT |
| MATCH THE 2017 FLORIDA BUILDING CODE ZONES. |
| |
| 5) FBC B 107.2.1, THE WIND LOAD SCHEDULE ON PAGE 8.0 |
| REFERS TO THE 2014 FLORIDA BUILDING CODE, THIS NEEDS TO |
| BE CHANGED TO THE 2017 FLORIDA BUILDING CODE. |
| |
| 6) FBC B 107.2.1, ON PAGE 6.0 DETAIL #1, THE ROOF PITCH |
| IS IDENTIFIED AS 6:12, ALL OTHER DETAILS ON PLANS SHOW |
| THE ROOF PITCH TO BE A 5:12. PLEASE CLARIFY THE |
| LOCATION OF 6:12 PITCH DETAIL. |
| |
| 7) FBC B 107.2.1 THE SUBMITTED PRODUCT APPROVAL FOR |
| SLIDING GLASS DOOR (14-1103.02) HAS EXPIRED. ON PAGE |
| 3.0 THE DOOR SCHEDULE IDENTIFIES THIS DOOR AS # 3, ON |
| THE FLOOR PLAN DOOR #3 IS FOR AN EXTERIOR SWINGING DOOR |
| NOT A SLIDING GLASS DOOR.PLEASE CORRECT THE DOOR |
| SCHEDULE AND SUBMIT THE CORRECT(REVIEW STAMPED) PRODUCT |
| APPROVAL FOR THIS LOCATION. |
| |
| 8) FBC B 107.2.1, THE SLIDING GLASS DOOR IDENTIFIED AS |
| DOOR # 2, PRODUCT APPROVAL # 17-0504.01 WAS NOT |
| SUBMITTED. PLEASE PROVIDE THE REVIEW STAMPED PRODUCT |
| APPROVAL. |
| |