Plan Review Notes
Plan Review Notes For Permit 20020504
Permit Number 20020504
Review Stop B
Sequence Number 1
Notes
Date Text
2020-02-25 10:51:19***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 1) FBC B 107.2.1, THE COVER PAGE CLASSIFIES THE
 OCCUPANCY AS R-2. THIS NEEDS TO BE CHANGED TO R-3.
  
 2) FBC R 310.2.1, PAGE 4.0 EGRESS WINDOW DETAIL SHOWS A
 MINIMUM CLEAR HEIGHT OF 22". THIS NEEDS TO BE CHANGED
 TO 24".
  
 3) FBC B 107.2.1, PAGES 9.0, 10.0, & 11.0 DO NOT
 IDENTIFY THE LOCATION OF BATHROOM DOOR/ENTRY. PLEASE
 SHOW ON PLANS.
  
 4) FBC R FIGURE R 301.2(7), ON PAGES 3.0 AND 8.0, THE
 WIND LOAD SCHEDULE ZONES FOR ROOF AND WALLS DO NOT
 MATCH THE 2017 FLORIDA BUILDING CODE ZONES.
  
 5) FBC B 107.2.1, THE WIND LOAD SCHEDULE ON PAGE 8.0
 REFERS TO THE 2014 FLORIDA BUILDING CODE, THIS NEEDS TO
 BE CHANGED TO THE 2017 FLORIDA BUILDING CODE.
  
 6) FBC B 107.2.1, ON PAGE 6.0 DETAIL #1, THE ROOF PITCH
 IS IDENTIFIED AS 6:12, ALL OTHER DETAILS ON PLANS SHOW
 THE ROOF PITCH TO BE A 5:12. PLEASE CLARIFY THE
 LOCATION OF 6:12 PITCH DETAIL.
  
 7) FBC B 107.2.1 THE SUBMITTED PRODUCT APPROVAL FOR
 SLIDING GLASS DOOR (14-1103.02) HAS EXPIRED. ON PAGE
 3.0 THE DOOR SCHEDULE IDENTIFIES THIS DOOR AS # 3, ON
 THE FLOOR PLAN DOOR #3 IS FOR AN EXTERIOR SWINGING DOOR
 NOT A SLIDING GLASS DOOR.PLEASE CORRECT THE DOOR
 SCHEDULE AND SUBMIT THE CORRECT(REVIEW STAMPED) PRODUCT
 APPROVAL FOR THIS LOCATION.
  
 8) FBC B 107.2.1, THE SLIDING GLASS DOOR IDENTIFIED AS
 DOOR # 2, PRODUCT APPROVAL # 17-0504.01 WAS NOT
 SUBMITTED. PLEASE PROVIDE THE REVIEW STAMPED PRODUCT
 APPROVAL.
  