2020-02-25 11:53:552017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20020502
 ADD: 1551 NORTH FLAGLER DR. SUITE LPH 14
 CONT: DRY ART CONSTRUCTION
 TEL: 561-436-3703
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 25/2020
 ACTION: DENIED
  
 1) THE DESCRIPTION OF WORK ON THE PERMIT APPLICATION
 AND WHAT IS REFERENCED ON THE FLOOR PLAN NEEDS
 CLARIFICATION. ON THE FLOOR PLAN IT STATES REMOVE TILE
 & INSTALL NEW TILE, KEEP TUB REPLACE VANITY AND TOILET.
 THE PERMIT APPLICATION UNDER THE DESCRIPTION OF WORK
 STATES CONVERT TUB TO SHOWER REPLACE SINK AND TOILET.
 DISCREPANCY IN THE DESCRIPTION OF WORK.
 W 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) THE SUBMITTED FLOOR PLAN DOES HAVE THE CONTRACTOR
 INFORMATION ON THE PLAN BUT THE PLANS IS SMALLER THAN
 1/8 INCH SCALE AND THE CLARITY OF THE PLAN THE WRITTEN
 WORDS WILL NOT TRANSFER WHEN SCANNED INTO THE COMPUTER
 FOR RECORD RETENTION.
 W 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE
 107.2.1.3 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER. THE BUILDING OFFICIAL MAY ESTABLISH
 THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS
 AND SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO
 ITS RECORD RETENTION PROGRAM. THIS POLICY
 MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE,
 CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS
 MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH
 THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES.
  
 3) IF THE TUB IS BEING REMOVED AND A SHOWER STALL IS
 BEING INSTALLED PLEASE SHOW COMPLIANCE WITH THE 2017
 FBC-B SECTION 2509.1 WET AREAS AND 2509.2 BASE FOR TILE
 AND 2509.3 LIMITATIONS.
 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS
 SHALL CONFORM TO SECTION 1210.2.
  
 2509.2 BASE FOR TILE. MATERIALS USED AS A BASE FOR TUBS
 AND SHOWER AREAS AND WALL AND CEILING PANELS IN SHOWER
 AREAS SHALL BE OF MATERIALS LISTED IN TABLE 2509.2 AND
 INSTALLED IN ACCORDANCE WITH THE MANUFACTURES
 RECOMMENDATIONS. WATER- RESISTANT GYPSUM BOARD SHALL BE
 USED AS A BASE FOR TILE IN WATER CLOSET COMPARTMENT
 WALLS WHEN INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM
 C840 AND THE MANUFACTURERS RECOMMENDATIONS. REGULAR
 GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR WALL PANELS
 IN OTHER WALL AND CEILING AREAS WHEN INSTALLED IN
 ACCORDANCE WITH GA-216 OR ASTM C840.
  
 TABLE 2509.2
 BACKER BOARD MATERIALS
  
 GLASS MAT GYPSUM BACKING PANEL ASTM C1178
 NONASBESTOS FIBER-CEMENT BACKER BOARD ASTM C1288 OR ISO
 8336/ CATEGORY C
 NONASBESTOS FIBER-MAT REINFORCED CEMENTITIOUS BACKER
 UNIT ASTM C1325.
  
 2509.3 LIMITATIONS. WATER-RESISTANT GYPSUM BACKING
 BOARD SHALL NOT BE USED IN THE FOLLOWING LOCATIONS:
 1) OVER A VAPOR RETARDER IN SHOWER OR BATHTUB
 COMPARTMENTS.
 2) WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN
 AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY.
  
 4) THE FLOOR PLAN DOES NOT MAKE IT CLEAR IF THE TILE
 FLOORS ARE ALSO BEING REMOVED. IF SO THEN COMPLIANCE
 WITH NEW FLOOR TILE AND SOUND PROOFING WILL NEED TO
 SHOW COMPLIANCE.
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2017)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS (NOT SALES BROCHURES)
 SHOWING COMPLIANCE WITH ALL 3 REQUIREMENTS:
  
 4A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.SHEET
  
 4B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 4C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 5) PLEASE REVIEW THE PLUMBING PLAN REVIEW COMMENT ON
 THE FAIR HOUSING REQUIREMENTS. FOR BOTH SHOWERS AND
 TUBS PLEASE REVIEW REQUIREMENT # 6 OF THE FAIR HOUSING
 GUIDE.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP & CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  