Review Stop G
Sequence Number 1
Notes
Date Text
2020-02-13 06:01:111) YOU HAVE SUBMITTED A PE PIPE SIZING SHEET WITH TWO
 DIFFERENT SIZING TABLES ON IT. WHICH ONE IS BEING USED
 TO SIZE THE PE SYSTEM? ALSO, WHERE IS THIS SIZING TABLE
 FROM? THE SYSTEM MUST BE SIZED BASED ON THE TABLES IN
 THE 2017 FBC-FUEL GAS CODE OR USING THE SIZING TABLES
 INCLUDED IN A LISTED PIPING SYSTEM'S MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. 2017 FBC-FUEL GAS CODE
 SEC.402.3.
 2) THE SIZING TABLE SUBMITTED FOR THE SCH. 40 METALLIC
 PIPE IS FROM THE UNIFORM PLUMBING CODE. THIS IS NOT A
 REFERENCED STANDARD IN THE 2017 FBC-FUEL GAS CODE OR
 PLUMBING CODE. THEREFORE THIS SIZING TABLE IS
 UNACCEPTABLE. SUBMIT A SIZING TABLE FROM ONE OF THE
 REQUIREMENTS IN THE 2017 FBC-FUEL GAS CODE SEC.402.3.
 3) SUBMIT TWO COPIES OF A HOUSE PLAN / FLOOR PLAN
 SHOWING THE LOCATION OF THE TANKLESS WATER HEATER AND
 THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR
 WINDOWS IN RELATION TO THE TANKLESS WATER HEATER. THE
 LOCATION OF THE TANKLESS WATER HEATER SHALL COMPLY WITH
 THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE HOUSE
 PLAN / FLOOR PLAN CAN BE HAND DRAWN. WPB AMEND. TO FBC
 SEC. 107.2.1.
 4) THE BTU LOAD OF THE RANGE ON THE GAS DRAWING IS
 SHOWN AS 28,100 BTU'S. ADDING UP THE BTU LOAD OF THE
 BURNER'S ON THE MANUFACTURER'S SPECIFICATION SHEET
 COMES TO 54,600 BTU'S. WHERE DDID THE 28,100 BTU LOAD
 COME FROM?
 5) A SEPARATE PERMIT WILL BE REQUIRED FOR THE ELECTRIC
 THAT NEEDS TO BE INSTALLED.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  