Plan Review Notes
Plan Review Notes For Permit 20020439
Permit Number 20020439
Review Stop G
Sequence Number 1
Notes
Date Text
2020-02-19 15:01:391) THE PLANS SHOW AN EXISTING GAS METER BUT CITY
 RECORDS DO NOT SHOW THAT A GAS SYSTEM WAS EVER
 PERMITTED FOR THIS ADDRESS. ALL EXISTING GAS PIPING,
 EQUIPMENT AND APPLIANCES MUST BE PERMITTED. WPB AMEND.
 TO FBC SEC.105.1.
 2) SHOW THE LOCATION OF THE TANKLESS WATER HEATER AND
 THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR
 WINDOWS IN RELATION TO THE TANKLESS WATER HEATER. THE
 LOCATION OF THE TANKLESS WATER HEATER SHALL COMPLY WITH
 THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. WPB
 AMEND. TO FBC SEC. 107.2.1.
 3) WHERE CONNECTED TO RIGID PIPING, A UNION SHALL BE
 INSTALLED WITHIN 1 FOOT OF EITHER SIDE OF THE MP
 REGULATOR. 2017 FBC-FUEL GAS SEC.410.2 (7), 2017 FBC-
 RESIDENTIAL SEC. G2421.2 (7).
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  