Plan Review Notes
Plan Review Notes For Permit 20020422
Permit Number 20020422
Review Stop B
Sequence Number 4
Notes
Date Text
2020-03-16 16:10:32ROOF RECOVER FOURTH BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- OK.
  
 ORIGINAL COMMENT:
 2- NEED FIELD UPLIFT TESTING TAS 105 AND MOISTURE
 CONTENT TEST TAS 126 (2 COPIES) AS REQUIRED BY NOTE #14
 ON PAGE 3 OF 67 OF FL16443-R17 FOR RECOVER
 INSTALLATIONS. NOTE: THIS NOTE STATES THAT FOR RECOVER
 INSTALLATIONS, THE EXISTING ROOF SHALL BE EXAMINED IN
 ACCORDANCE WITH FBC 1521.
 THE REQUIRED TESTS ARE TO VERIFY THAT EXISTING ROOF IS
 ADEQUATE FOR RECOVER INSTALLATION.
  
 RESPONSE:
 NEED FIELD UPLIFT TESTING TAS 105 AND MOISTURE CONTENT
 TEST TAS 126. THESE TESTS NEED TO BE DONE BY AN
 APPROVED TESTING AGENCY AND ALL TEST REPORTS, INCLUDING
 CALCULATIONS SHALL BE SIGNED BY A REGISTERED DESIGN
 PROFESSIONAL. SEE SCOPE ON TESTING APPLICATION
 STANDARDS 105 AND 126 RESPECTIVELY. TESTING SUBMITTED
 IS NOT DONE BY AN APPROVED TESTING AGENCY AND IS NOT
 SIGNED BY REGISTERED DESIGN PROFESSIONAL.
 SEC. 107.2.1 CITY AMENDMENTS.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]