2020-02-26 15:19:26ROOF RECOVER SECOND BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- MAXIMUM DESIGN PRESSURES FOR SELECTED ASSEMBLY SC-95
 FROM FLORIDA PRODUCT APPROVAL FL16443-R17 DOESN'T MEET
 THE DESIGN PRESSURE FOR ALL ROOF ZONES. SEC. 1609.1
 FBC-BUILDING.
 NEED TO PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS
 (2 COPIES) AS REQUIRED BY NOTE#9 ON PAGE 2 OF 67 OF
 PRODUCT APPROVAL SUBMITTED.
  
 RESPONSE:
 RAS 117 CALCULATIONS SUBMITTED NEED TO BE REVISED.
 ENGINEER STATED THAT CONCRETE FASTENERS NEED TO HAVE
 MIN. 1 INCH EMBEDMENT. ACCORDING TO NOTE #2 ON PAGE 2
 OF 67 OF FLORIDA PRODUCT APPROVAL FL16443-R17
 SUBMITTED, THE MINIMUM EMBEDMENT REQUIRED IS 1.25
 INCHES. ENGINEER TO REVISE SPECIFICATIONS OR PROVIDE
 COMPLETE ENGINEERING SHOWING THAT THE 1 INCHE EMBEDMENT
 IS ADEQUATE. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 2- NEED FIELD UPLIFT TESTING TAS 105 AND MOISTURE
 CONTENT TEST TAS 126 (2 COPIES) AS REQUIRED BY NOTE #14
 ON PAGE 3 OF 67 OF FL16443-R17 FOR RECOVER
 INSTALLATIONS. NOTE: THIS NOTE STATES THAT FOR RECOVER
 INSTALLATIONS, THE EXISTING ROOF SHALL BE EXAMINED IN
 ACCORDANCE WITH FBC 1521.
 THE REQUIRED TESTS ARE TO VERIFY THAT EXISTING ROOF IS
 ADEQUATE FOR RECOVER INSTALLATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,