2020-02-26 15:19:26 | ROOF RECOVER SECOND BUILDING REVIEW CHECKLIST. |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| 1- MAXIMUM DESIGN PRESSURES FOR SELECTED ASSEMBLY SC-95 |
| FROM FLORIDA PRODUCT APPROVAL FL16443-R17 DOESN'T MEET |
| THE DESIGN PRESSURE FOR ALL ROOF ZONES. SEC. 1609.1 |
| FBC-BUILDING. |
| NEED TO PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS |
| (2 COPIES) AS REQUIRED BY NOTE#9 ON PAGE 2 OF 67 OF |
| PRODUCT APPROVAL SUBMITTED. |
| |
| RESPONSE: |
| RAS 117 CALCULATIONS SUBMITTED NEED TO BE REVISED. |
| ENGINEER STATED THAT CONCRETE FASTENERS NEED TO HAVE |
| MIN. 1 INCH EMBEDMENT. ACCORDING TO NOTE #2 ON PAGE 2 |
| OF 67 OF FLORIDA PRODUCT APPROVAL FL16443-R17 |
| SUBMITTED, THE MINIMUM EMBEDMENT REQUIRED IS 1.25 |
| INCHES. ENGINEER TO REVISE SPECIFICATIONS OR PROVIDE |
| COMPLETE ENGINEERING SHOWING THAT THE 1 INCHE EMBEDMENT |
| IS ADEQUATE. SEC. 107.2.1.2 CITY AMENDMENTS. |
| |
| 2- NEED FIELD UPLIFT TESTING TAS 105 AND MOISTURE |
| CONTENT TEST TAS 126 (2 COPIES) AS REQUIRED BY NOTE #14 |
| ON PAGE 3 OF 67 OF FL16443-R17 FOR RECOVER |
| INSTALLATIONS. NOTE: THIS NOTE STATES THAT FOR RECOVER |
| INSTALLATIONS, THE EXISTING ROOF SHALL BE EXAMINED IN |
| ACCORDANCE WITH FBC 1521. |
| THE REQUIRED TESTS ARE TO VERIFY THAT EXISTING ROOF IS |
| ADEQUATE FOR RECOVER INSTALLATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |