2020-02-12 10:53:22ROOF RECOVER BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- MAXIMUM DESIGN PRESSURES FOR SELECTED ASSEMBLY SC-95
 FROM FLORIDA PRODUCT APPROVAL FL16443-R17 DOESN'T MEET
 THE DESIGN PRESSURE FOR ALL ROOFF ZONES. SEC. 1609.1
 FBC-BUILDING.
 NEED TO PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS
 (2 COPIES) AS REQUIRED BY NOTE#9 ON PAGE 2 OF 67 OF
 PRODUCT APPROVAL SUBMITTED.
  
 2- NEED FIELD UPLIFT TESTING TAS 124 (2 COPIES) AS
 REQUIRED BY NOTE #12 ON PAGE 3 OF 67 OF FL16443-R17
 FOR BONDED INSULATION OR MEMBRANE OVER EXISTING
 SUBSTRATES IN A RECOVER INSTALLATION.
 FAC 61G20-3.001SEC. 1609.1 FBC-BUILDING.
  
 3- NEED FIELD UPLIFT TESTING TAS 105 AND MOISTURE
 CONTENT TEST TAS 126 (2 COPIES) AS REQUIRED BY NOTE #14
 ON PAGE 3 OF 67 OF FL16443-R17 FOR RECOVER
 INSTALLATIONS. NOTE: THIS NOTE STATES THAT FOR RECOVER
 INSTALLATIONS, THE EXISTING ROOF SHALL BE EXAMINED IN
 ACCORDANCE WITH FBC 1521.
 THE REQUIRED TESTS ARE TO VERIFY THAT EXISTING ROOF IS
 ADEQUATE FOR RECOVER INSTALLATION.
  
 4-THERE ARE SEVERAL BUILDINGS AND ROOF AREAS IN THIS
 PROPERTY. PROVIDE SKETCH (2 COPIES) SHOWING THE ROOF
 AREA WHERE WORK IS GOING TO TAKE PLACE. SEC. 107.2.1
 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION