2020-02-20 10:02:021ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20020370
 2/20/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1: REFER TO THE BUILDING REVIEW COMMENTS.
 THERE ARE MISSING ARCHITECTURAL AND LIFE SAFETY PLAN
 DETAILS THAT WILL EFFECT THE NEW AC DUCT PLANS. BASED
 ON THE CURRENT PLANS AND THE COMMENTS IT APPEARS THAT
 FIRE DAMPERS ARE MSSING FROM THE DUCT PENETRATIONS AT
 THE FIRE-RATED STAIRWELL WALLS, AND FOR ALL ALL THE
 SUPPLY DIFFUSER PENETRATIONS OF THE FIRE-RATED
 FLOOR/CEILING ASSEMBLY- SEE SECTION 607.5.2 & 607.6.1.
 IT WOULD BE HELPFUL TO PROVIDE A REFLECTIVE CEILING
 PLAN AND A BUILDING SECTION CUT TO CLARIFY HIOW THE
 DUCTS WILL BE RUN THROUGHOUT THE FIRST FLOOR- SECTION
 107.2.1 WPB.
  
 2) M1: CLARIFY HOW AIR IS BEING RETURNED TO AHU-2-
 SECTION 601.6 FBC M. THERE DOESN'T APPEAR TO BE A MAIN
 RETURN GRILL IN THE STAIRWELL WALL OR DOOR. PLEASE NOTE
 THAT ANY OPENINGS IN THE WALL OR DOOR WOULD REQUIRE
 FIRE DAMPERS- SECTION 607.5.2.
  
 3) M1: THE PLAN SHOWS A NEW LAB WHICH MAY REQUIRE A
 DEDICATED EXHAUST VENTILATION SYSTEM. PLEASE SEE
 SECTION 510.1 FBC M AND PROVIDE A BRIEF NARREATIVE ON
 THE PLAN DESCRIBING THE WORK THAT WILL BE PERFORMED IN
 THE LAB, AND MATERIALS THAT WILL BE PROCESS AND/OR
 STORED THERE. FOR THE PURPOSES OF THE PROVISIONS OF
 SECTION 510, A LABORATORY SHALL BE DEFINED AS A
 FACILITY WHERE THE USE OF CHEMICALS IS RELATED TO
 TESTING, ANALYSIS, TEACHING, RESEARCH OR DEVELOPMENTAL
 ACTIVITIES. CHEMICALS ARE USED OR SYNTHESIZED ON A
 NONPRODUCTION BASIS, RATHER THAN IN A MANUFACTURING
 PROCESS.
  
 4) SHOW THE LOCATION OF THE NEW CONDENSER ON THE ROOF.
 PLEASE REFER TO BUILDING REVIEW COMMENT #13 ABOUT THE
 AC STAND AND SHOW COMPLIANCE.
  
 5) THE AC CALCULATIONS ARE LISTING THE PROJECT LOCATION
 AS PALM BEACH GARDENS- PLEASE CORRECT- SECTION C403.2.1
 FBC M.
  
 6) PROVIDE A PRODUCT DATA SUBMITTAL FOR THE MOTORIZED
 DAMPERS WITH REVIEW AND APPROVAL STAMP BY THE EOR-
 SECTION 107.2.1 WPB & SECTION C403.2.4.3 FBC EC. PLEASE
 NOTE THE SUBMITTAL MAY BE DEFERRED PER SECTION
 107.3.4.2 WPB.
  
 7) M1: ACCESS PANELS SHALL BE PROVIDED FOR THE
 MOTORIZED DAMPERS IF TO BE LOCATED ABOVE A DRYWALL
 CEILING- SECTION 306.1 FBC M.
  
 8) M1: PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE AIR
 HANDLERS- SECTION 307.2.3 FBC M. PLEASE NOTE THAT
 COMNDESNATE SHALL NOT BE DISCHARGED INTO THE CITY
 ANITARY SYSTEM- SECTIOB
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  