2020-02-20 10:02:02 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #20020370 |
| 2/20/20 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M1: REFER TO THE BUILDING REVIEW COMMENTS. |
| THERE ARE MISSING ARCHITECTURAL AND LIFE SAFETY PLAN |
| DETAILS THAT WILL EFFECT THE NEW AC DUCT PLANS. BASED |
| ON THE CURRENT PLANS AND THE COMMENTS IT APPEARS THAT |
| FIRE DAMPERS ARE MSSING FROM THE DUCT PENETRATIONS AT |
| THE FIRE-RATED STAIRWELL WALLS, AND FOR ALL ALL THE |
| SUPPLY DIFFUSER PENETRATIONS OF THE FIRE-RATED |
| FLOOR/CEILING ASSEMBLY- SEE SECTION 607.5.2 & 607.6.1. |
| IT WOULD BE HELPFUL TO PROVIDE A REFLECTIVE CEILING |
| PLAN AND A BUILDING SECTION CUT TO CLARIFY HIOW THE |
| DUCTS WILL BE RUN THROUGHOUT THE FIRST FLOOR- SECTION |
| 107.2.1 WPB. |
| |
| 2) M1: CLARIFY HOW AIR IS BEING RETURNED TO AHU-2- |
| SECTION 601.6 FBC M. THERE DOESN'T APPEAR TO BE A MAIN |
| RETURN GRILL IN THE STAIRWELL WALL OR DOOR. PLEASE NOTE |
| THAT ANY OPENINGS IN THE WALL OR DOOR WOULD REQUIRE |
| FIRE DAMPERS- SECTION 607.5.2. |
| |
| 3) M1: THE PLAN SHOWS A NEW LAB WHICH MAY REQUIRE A |
| DEDICATED EXHAUST VENTILATION SYSTEM. PLEASE SEE |
| SECTION 510.1 FBC M AND PROVIDE A BRIEF NARREATIVE ON |
| THE PLAN DESCRIBING THE WORK THAT WILL BE PERFORMED IN |
| THE LAB, AND MATERIALS THAT WILL BE PROCESS AND/OR |
| STORED THERE. FOR THE PURPOSES OF THE PROVISIONS OF |
| SECTION 510, A LABORATORY SHALL BE DEFINED AS A |
| FACILITY WHERE THE USE OF CHEMICALS IS RELATED TO |
| TESTING, ANALYSIS, TEACHING, RESEARCH OR DEVELOPMENTAL |
| ACTIVITIES. CHEMICALS ARE USED OR SYNTHESIZED ON A |
| NONPRODUCTION BASIS, RATHER THAN IN A MANUFACTURING |
| PROCESS. |
| |
| 4) SHOW THE LOCATION OF THE NEW CONDENSER ON THE ROOF. |
| PLEASE REFER TO BUILDING REVIEW COMMENT #13 ABOUT THE |
| AC STAND AND SHOW COMPLIANCE. |
| |
| 5) THE AC CALCULATIONS ARE LISTING THE PROJECT LOCATION |
| AS PALM BEACH GARDENS- PLEASE CORRECT- SECTION C403.2.1 |
| FBC M. |
| |
| 6) PROVIDE A PRODUCT DATA SUBMITTAL FOR THE MOTORIZED |
| DAMPERS WITH REVIEW AND APPROVAL STAMP BY THE EOR- |
| SECTION 107.2.1 WPB & SECTION C403.2.4.3 FBC EC. PLEASE |
| NOTE THE SUBMITTAL MAY BE DEFERRED PER SECTION |
| 107.3.4.2 WPB. |
| |
| 7) M1: ACCESS PANELS SHALL BE PROVIDED FOR THE |
| MOTORIZED DAMPERS IF TO BE LOCATED ABOVE A DRYWALL |
| CEILING- SECTION 306.1 FBC M. |
| |
| 8) M1: PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE AIR |
| HANDLERS- SECTION 307.2.3 FBC M. PLEASE NOTE THAT |
| COMNDESNATE SHALL NOT BE DISCHARGED INTO THE CITY |
| ANITARY SYSTEM- SECTIOB |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |