2020-02-19 13:07:12 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 20020370 |
| ADD: 416 CLEMATIS ST. |
| CONT: GM CONSTRUCTION |
| TEL: 561-742-3200 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION. |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. FEB. 19TH/ 2020 |
| ACTION: DENIED |
| |
| 1) DISCREPANCY IN PLANS SHEET A-3 DETAIL # 2 IS FOR A 1 |
| HOUR FIRE RATED WALL. THIS DETAIL SHOWS A 20 FT. PLUS |
| 25 GAUGE 3 5/8 INCH STEEL STUD WHEREAS THE STRUCTURAL |
| SHEET S100 DETAIL # 6 SHOWS STRUCTURAL STEEL STUD |
| 400S200-43 AND PLATFORM CONSTRUCTION WITH THE 2ND FLOOR |
| FRAMING AND FLOOR SHEATHING. THIS PLAN DOES NOT SHOW |
| THE 2ND FLOOR WALL OF THE STAIRWELL NOR A FIRE RATING |
| OR ANY FIRE RATED DRYWALL. THE STRUCTURAL DETAIL ALSO |
| INDICATES THERE TO BE A LAYER OF 5/8 INCH APA PLYWOOD |
| TO BE APPLIED TO BOTH SIDES OF THE STRUCTURAL STEEL |
| STUD CREATING THE STAIRWELL TO THE 2ND FLOOR. |
| 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1 ADMINISTRATIVE CODE SECTION 107.2.1.2 |
| ADDITIONAL INFORMATION IS REQUIRED. DISCREPANCY IN |
| PLANS. |
| 2017 FBC-B SECTION 1023.2. CONSTRUCTION. ENCLOSURES FOR |
| INTERIOR EXIT STAIRWAYS SHALL BE CONSTRUCTED AS FIRE |
| BARRIERS IN ACCORDANCE WITH SECTION 707 OF THE FBC-B. |
| THE FIRE RESISTANCE RATING OF NOT LESS THAN 1 HOUR FOR |
| A 2 STORY BUILDING. PLEASE PROVIDE THE UL FIRE RATING |
| FOR THE ASSEMBLY INCLUDING THE 5/8 INCH PLYWOOD |
| SUB-SHEATHING AND OR GYPSUM ASSOCIATION LISTING. |
| |
| 2) THE HEIGHT OF THE 2ND FLOOR IS NOT GIVEN NEITHER THE |
| TOP ROUGH FRAMING HEIGHT, NOR FLOOR FINISH ON THE A1 |
| SHEET, A2 SHEET, THE INSET STAIR DETAIL FOUND ON SHEET |
| A1 REFERENCES SEE THE STRUCTURAL SHEET S100. THE |
| STRUCTURAL SHEET S100 DOES NOT PROVIDE AT WHAT HEIGHT |
| THE FINISH FLOOR IS OR THE TOP OF THE STEEL FLOOR |
| JOIST. |
| 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 3) SHEET A1 DETAIL FOR TYPICAL STAIR SECTION IS NOT |
| DRAWN FOR THIS APPLICATION, THERE IS A MID-LANDING |
| SHOWN IN THE TYPICAL DETAIL WHEREAS BOTH THE |
| ARCHITECTURAL AND STRUCTURAL FLOOR PLAN DOES NOT SHOW A |
| MID-LANDING AND EITHER A 90 DEGREE OR 180 DEGREE TURN |
| AT THE MID-LANDING. THE SHEET A-1 STAIR DETAIL DOES NOT |
| GIVE THE RISE NOR RUN FOR RISER AND TREAD (FBC-B |
| 1011.5.2 RISER HEIGHT AND TREAD DEPTH) DOES THE PLAN |
| STATE THE TREAD IS TO BE 2 INCH CONCRETE SLAB ON STEEL |
| PAN WHEREAS THE SHEET S100 DETAIL # 6 INDICATES THE |
| STAIR TREAD TO BE A 2X12, AGAIN DISCREPANCY IN PLANS. |
| THE ARCHITECTURAL PLAN SHOWS A STEEL STAIR CARRIAGE |
| WHEREAS THE STRUCTURAL PLAN DETAIL # 6 SHOWS THE 2X12 |
| TREADS ANCHORED WITH 4X4 STEEL ANGLE SUPPORTS BENEATH |
| THE TREAD ANCHORED INTO THE VERTICAL FRAMING MEMBERS, |
| AGAIN DISCREPANCY BETWEEN THE 2 PLANS. |
| |
| 4A) SHEET A-1 THE FLOOR PLAN SHOWS BENEATH THE |
| STAIRWELL A NEW AHU-2 UNIT. THE WALLS AROUND THE |
| STAIRWELL ARE SHOWN AS WALL TYPE G A ONE-HOUR FIRE |
| RATED WALL, BUT THERE IS NO MENTION AS TO THE FIRE |
| RATING OF THE CEILING UNDER THE STAIRWELL. SEE 2017 |
| FBC-B 1011.7.3 ENCLOSURES UNDER STAIRWAYS. |
| |
| 4B) SHEET M-1 SHOWS A AHU-2 AIR HANDLER UNDER THE FIRE |
| RATED STAIRS, WHICH REQUIRES A 1 HOUR FIRE RATED WALLS |
| (2017 FBC-B 1011.7.3) AND FIRE DAMPERS IN COMPLIANCE |
| WITH (2017 FBC-B 717.3.2.1). |
| |
| 5) SHEET A-1 DOOR # 15 INSWING DOOR IT APPEARS THERE |
| MAY NOT BE 18 INCHES ON THE LATCH SIDE OF THE DOOR. THE |
| PLANS WILL NEED TO SHOW COMPLIANCE WITH THE 2017 |
| ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES. FIGURE |
| 404.2.4.1(A). DOORS. MINIMUM MANEUVERING CLEARANCES AT |
| DOORS AND GATES SHALL COMPLY WITH 404.2.4. MANEUVERING |
| CLEARANCES SHALL EXTEND THE FULL WIDTH OF THE DOORWAY |
| AND THE REQUIRED LATCH SIDE FOR SIDE CLEARANCE. |
| |
| 6A) SHEET A-1 IN LAB ROOM 114 THERE IS A DETAIL 2/A-2. |
| THE LAB SINK IS AT 36 INCHES IN HEIGHT. PLEASE REVIEW |
| THE 2017 FBC-ACCESSIBILITY CODE CHARGING SECTION 212.3. |
| SINKS. WHERE SINKS ARE PROVIDED, AT LEAST 5 PERCENT, |
| BUT NOT FEWER THAN ONE, OF EACH TYPE PROVIDED IN EACH |
| ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606. |
| |
| 6B) 2017 FBC-ACCESSIBILITY CODE 606.2 CLEAR FLOOR |
| SPACE. A CLEAR FLOOR SPACE COMPLYING WITH 305, |
| POSITIONED FOR A FORWARD APPROACH, AND KNEE AND TOE |
| CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED. |
| EXCEPTIONS: |
| 1.A PARALLEL APPROACH COMPLYING WITH 305 SHALL BE |
| PERMITTED TO A KITCHEN SINK, IN A SPACE WHERE A COOK |
| TOP OR CONVENTIONAL RANGE IS NOT PROVIDED, AND TO WET |
| BARS. |
| |
| 6C) 2017 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT. |
| LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT |
| OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES |
| MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| |
| 6D) 2017 FBC-ACCESSIBILITY CODE 606.4 FAUCETS. CONTROLS |
| FOR FAUCETS SHALL COMPLY WITH 309. HAND-OPERATED |
| METERING FAUCETS SHALL REMAIN OPEN FOR 10 SECONDS |
| MINIMUM. |
| |
| 6E) 2017 FBC-ACCESSIBILITY CODE 606.5 EXPOSED PIPES AND |
| SURFACES. WATER SUPPLY AND DRAIN PIPES UNDER LAVATORIES |
| AND SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TO |
| PROTECT AGAINST CONTACT. THERE SHALL BE NO SHARP OR |
| ABRASIVE SURFACES UNDER LAVATORIES AND SINKS. |
| |
| 7) SHEET A-1 INDICATES THERE WILL BE AN EXCHANGE OF |
| DRINKING FOUNTAINS A SINGLE FOUNTAIN FOR A HIGH/ LOW |
| ADA DRINKING FOUNTAIN. THERE IS NO SECTION OR DETAIL |
| THROUGH THIS AREA NOR MENTION OF COMPLIANCE WITH THE |
| 2017 FBC-ACCESSIBILITY CODE FOR PROTRUDING OBJECTS SEE |
| THE ACCESS. CODE 307.2. THE CONCERN IS WITH THE HIGH |
| SIDE DRINKING FOUNTAIN, THE BOTTOM OF THE DRINKING |
| FOUNTAIN MAYBE HIGHER THAN THE LEADING EDGE A MAXIMUM |
| ALLOWABLE 27 INCHES FROM FINISH FLOOR. SEE FIGURE |
| 307.2. |
| |
| 8) SHEET A1 AND A2 SHOW DIFFERENT FIRE AREAS. SHEET A-1 |
| SHOWS A MERCANTILE OCCUPANCY ON THE 1ST FLOOR WHEREAS |
| THE 2ND FLOOR SHOWS A PROPOSED BUSINESS OCCUPANCY. |
| SHEET A-3 DETAIL # 1 SHOWS THE FLOOR CEILING ASSEMBLY |
| WITHOUT ANY HORIZONTAL FIRE BARRIER AS REQUIRED BY THE |
| 2017 FBC-B TABLE 707.3.10. THE TABLE INDICATES FOR |
| MERCANTILE/ BUSINESS A MIXED OCCUPANCY A 2 HOUR FIRE |
| BARRIER WOULD BE REQUIRED. |
| |
| 8A) IN THIS SET OF PLANS 1ST REVIEW THERE ARE NO |
| REFLECTIVE CEILING PLANS. 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATIVE CODE SECTION: |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE |
| EXAMINATION OF THE DOCUMENTS BY |
| THE BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING |
| MINIMUM CRITERIA AND DOCUMENTS: A FLOOR PLAN; |
| REFLECTIVE CEILING PLAN, FLOOR CEILING PLAN,? |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| 107.3.5.1.1 BUILDING |
| (8) FLOOR SYSTEMS |
| |
| 8B) THE M-1 MECHANICAL PLAN SHOWS THE 1ST FLOOR TRUNK |
| LINES THAT RUN 90 DEGREES TO THE STEEL FLOOR JOIST, ARE |
| THESE TRUNK LINES BELOW THE FIRE RATED 1ST FLOOR |
| CEILING? THERE ARE NO CUT SECTIONS THROUGH THE BUILDING |
| SHOWING THE LOCATION OF THIS SYSTEM. IF THE A/C TRUNK |
| LINES ARE ABOVE THE REQUIRED 2 HOUR FIRE RATED CEILING |
| THEN ALL PENETRATIONS OF THE RATED CEILING WILL NEED |
| CEILING RADIATE DAMPERS. 2017 FBC-B 717.3.3.4. |
| |
| 8C) THE SAME SITUATION OCCURS IN THE 1ST FLOOR CEILING |
| OF NOVEAU HEALTH AND WELLNESS THE ELECTRICAL SHEET E-2 |
| SHOWS 6 INCH DOWN LIGHTS PENETRATING THE 2 HOUR FIRE |
| RATED CEILING, PLEASE SHOW HOW COMPLIANCE WILL BE MET |
| FOR SECTION FBC-B 714.4. |
| |
| 9) NOTE NO ACTION REQUIRED. COMPONENTS AND CLADDING |
| PRESSURES FOR WALL ZONES 4 & 5 IN VASD ARE GOOD. |
| |
| 10) COMPONENTS AND CLADDING REQUIRES COMPLIANCE WITH |
| 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(A) EXTERIOR DOORS ,MULLIONS |
| (B) WINDOWS & MULLIONS |
| (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, |
| (G) PRE-ENGINEERED A/C STANDS |
| |
| 11) IDENTIFY GLAZING/ MULLIONS. THE SUBMITTED PRODUCT |
| APPROVALS THE ELEMENTS LISTED BELOW ARE NOT IDENTIFIED. |
| PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE |
| SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION |
| TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH |
| GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, |
| TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED |
| OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B |
| 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| |
| 12) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| |
| 13) THE ROOF TOP A/C STAND PRODUCT APPROVAL A |
| MIAMI-DADE NOA # 17-1218.02 WAS SUBMITTED, NOT REVIEWED |
| BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE |
| FOLLOWING REQUIREMENTS CALCULATING THE AREA (SIDE VIEW) |
| OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND, |
| THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS, |
| WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES, |
| ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE |
| STAND AND THE STAND TO THE ROOF. THE PRODUCT APPROVAL |
| IS TO BE REVIEWED BY THE DESIGNER OF RECORD, APPROVED |
| BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. |
| |
| 14) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| DEFERRAL OF ANY SUBMITTAL ITEMS (COMPONENT & CLADDING |
| PRODUCT APPROVALS) SHALL HAVE THE PRIOR APPROVAL OF THE |
| BUILDING OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL |
| IN RESPONSIBLE CHARGE SHALL LIST THE DEFERRED |
| SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY |
| THE BUILDING OFFICIAL. |
| |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. |
| |
| 15) SHEET S-100: |
| PLAN ORIENTATION TO NORTH. THE LEFT SIDE OF THE PLAN |
| FRONT OF BUILDING IS NORTH, TOP OF PLAN IS EAST, THE |
| RIGHT HAND SIDE OF THE PLAN IS SOUTH AND THE BOTTOM OF |
| THE PLAN IS WEST. IN THE |
| |
| 15A) SHEET S-100 INDICATES COLUMN TYPE C-1. SECTION 7 |
| SHOWS THE REQUIREMENT TO WELD BOTH TOP AND BOTTOM |
| PLATES TO THE HSS 4X4X ? INCH STEEL COLUMN. THERE IS A |
| SECOND DETAIL B THAT REQUIRES A BUILT UP BEAM TO BE |
| WELDED TO THE COLUMN. THERE IS NO WELDING MARKINGS |
| INDICATING THE TYPE OF WELD, THICKNESS OF WELD, AND |
| LENGTH OF WELDS. 2017 FBC-B 2204.1. |
| |
| 15B) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS |
| REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS & |
| WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN |
| ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF |
| INSPECTION. IN ACCORDANCE WITH THE AMERICAN WELDING |
| SOCIETY. |
| 2017 FBC-B 2204.1 WELDING. AMERICAN WELDING SOCIETY AWS |
| B2.1 SPECIFICATIONS FOR WELDING PROCEDURES AND |
| PERFORMANCE QUALIFICATIONS. WELDS WILL NEED TO BE |
| REVIEWED BY AN INDEPENDENT 3RD PARTY AGENCY. |
| 2017 FBC-B 2204.2 BOLTING. |
| IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS |
| FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING |
| INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU. |
| |
| 15C) AS STATED IN COMMENT # 2 THERE IS NO HEIGHT GIVEN |
| FOR THE TOP OF THE 2ND FLOOR, FLOOR JOIST OR THE HEIGHT |
| OF THE FINISH FLOOR. THERE ARE DETAILS 1-7, B & C BUT |
| NONE OF THESE DETAILS PROVIDE THE 2ND FLOOR FINISH |
| FLOOR OR TOP OF JOIST ELEVATION. THIS WILL BE CRITICAL |
| TO BE ABLE TO DETERMINE THE PROPOSED HEIGHTS OF THE |
| STEEL STUD LOAD BEARING WALLS AS WE LL AS THE HEIGHTS |
| OF THE C1 COLUMN TYPES. 107.2.1.2 ADDITIONAL |
| INFORMATION IS REQUIRED. |
| |
| 15D) IN THE DETAIL B THERE IS A JOIST THAT APPEARS TO |
| RUN NORTH TO SOUTH AND THE JOIST ATTACHES TO THE EMBED |
| PLATE AT 16 AND THE OTHER END TO THE COLUMN C1. THIS |
| SITUATION IT WOULD APPEAR HAPPENS TWICE, AT EACH OF THE |
| C-1 COLUMNS. THERE IS NO JOIST SIZE AT THE DETAIL B NOR |
| ON THE JOIST LAYOUT PLAN. THE 2ND ISSUE WITH THIS |
| DETAIL THERE IS NO CONNECTION INFORMATION, IS THE |
| CONNECTION A WELD, BOLT AND OR SELF DRILLING SCREW? |
| 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 15E) QUESTION, AS TO WHAT TYPE OF FRAMING IS OVER THE |
| NORTH STOREFRONT WINDOW/ DOOR SYSTEM, IS THERE JUST A |
| SINGLE FJ3 CEILING JOIST OR IS THERE A BOX BEAM |
| (LINTEL) TO HELP TRANSFER THE WIND LOADS THAT ARE BEING |
| TRANSFERRED INTO THE FRAMING MEMBER ABOVE, PART OF THE |
| MWFRS (MAIN WIND FORCE RESISTING SYSTEM). THE NOTE IN |
| DETAIL MAKES IT SOUND AS IF THE BEAM AND COLUMN ARE TO |
| BE WELDED TOGETHER? 107.2.1.2 ADDITIONAL INFORMATION IS |
| REQUIRED. |
| |
| 15F) IN DETAIL C THE TOP OF THE CEILING JOIST IS AT |
| ELEVATION 8 FEET 9 ? INCHES, THE STRUCTURAL FRAMING |
| MEMBER IS 8 INCHES IN HEIGHT, BOTTOM OF JOIST IS 8 FEET |
| 1 ? ABOVE THE FINISH FLOOR. THE PLAN CALLS OUT FOR THE |
| ATTACHMENT OF 5/8 INCH THICK PLYWOOD AND THEN AND THEN |
| STUCCO. THERE IS NO MENTION IN EITHER THE ARCHITECTS |
| PLAN NOR THE SHEET S-100 THE REQUIREMENTS FOR |
| PROTECTING OF THE PLYWOOD (WATER-RESISTIVE BARRIER |
| FBC-B 2510.6), NOR THE LATHING AND FURRING FOR WIRE |
| LATH 2510.3 AND ASTM C 1063 REQUIREMENTS. |
| |
| 15G) THE SHEET S-100 IS SILENT AS TO THE VERTICAL |
| FRAMING MEMBERS, MULLIONS FOR THE WINDOW WALL SYSTEM |
| AND EXTERIOR DOORS. WHICH DESIGN PROFESSIONAL IS GOING |
| TO TAKE THE RESPONSIBILITY FOR REVIEWING THE COMPONENTS |
| AND CLADDING THAT ARE GOING TO BE ANCHORED TO THE NEW |
| STEEL FRAMING MEMBERS? THE STRUCTURAL ENGINEER OR THE |
| DESIGNER OF RECORD? |
| W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 16) IMPACT FEES- PAPER SUBMITTALS. PLANS REQUIRE REVIEW |
| BY THE PBC IMPACT FEE OFFICE. CALL (561) 233-5025. UPON |
| APPROVAL, YOU MAY CHECK OUT ONE PLAN SET AND TAKE TO |
| THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED AND |
| WITH A COPY OF THE RECEIPT AS APPLICABLE. PLEASE |
| PROVIDE THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO |
| THE PBC IMPACT FEE OFFICE. THE FORM CAN BE FOUND AT: |
| HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPAC |
| TFEES/FORMS/QUESTIONNAIRE.PDF |
| |
| 17) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |