Plan Review Notes
Plan Review Notes For Permit 20020275
Permit Number 20020275
Review Stop G
Sequence Number 2
Notes
Date Text
2020-03-30 11:13:22PLAN REVIEW - GAS
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER ? BUILDING - PX3169
 PLANS EXAMINER ? 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
  
 1ST REVIEW
  
 1. FBC 107.2.1 PROVIDE COMPLETE INSTALLATION PLAN
 DRAWING FOR RELOCATION OF EXISTING GAS WATER HEATER,
 INCLUDING GAS RISER DIAGRAM INCLUDING ANY OTHER
 EXISTING APPLIANCES AND BTUH VALUES, PIPE SIZING
 CRITERIA, WHERE EXISTING IS LOCATED, EXISTING PIPING ON
 PLAN, HOW IT IS TO BE RE ROUTED, PIPING MATERIALS AND
 VALVING, CONFIRM THE EXISTING WATER HEATER IS FOR
 OUTDOOR INSTALLATION AND SUBMIT WATER HEATER
 INSTALLATION MANUAL. THIS IS A SECOND REQUEST.
 2. FBC 107.2.1 NOTE ON DRAWING SAYS SEE ATTACHED SPEC
 FOR EXISTING WATER HEATER AND I FIND NONE UPLOADED TO
 THE PROJECT FOR REVIEW.
 3. FBC FUEL GAS SECTION 404. PLEASE NOT THAT PIPING IN
 CONCEALED LOCATIONS SHALL NOT HAVE UNIONS, TUBING
 FITTINGS, RIGHT AND LEFT COUPLINGS, BUSHINGS,
 COMPRESSION COUPLINGS AND SWING JOINTS MADE BY
 COMBINATIONS OF FITTINGS UNLESS THE FITTINGS ARE LISTED
 FOR USE IN CONCEALED LOCATIONS.
  
 REVIEWED REMOTELY BY JAMES BAKER, PE
 PX3997, PE77268
 561-805-6724
 [email protected]
  
  
  
  
  
  