2020-03-30 11:13:22 | PLAN REVIEW - GAS |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER ? BUILDING - PX3169 |
| PLANS EXAMINER ? 1&2 FAMILY - SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 2ND REVIEW |
| |
| RESULTS: DENIED |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| |
| 1ST REVIEW |
| |
| 1. FBC 107.2.1 PROVIDE COMPLETE INSTALLATION PLAN |
| DRAWING FOR RELOCATION OF EXISTING GAS WATER HEATER, |
| INCLUDING GAS RISER DIAGRAM INCLUDING ANY OTHER |
| EXISTING APPLIANCES AND BTUH VALUES, PIPE SIZING |
| CRITERIA, WHERE EXISTING IS LOCATED, EXISTING PIPING ON |
| PLAN, HOW IT IS TO BE RE ROUTED, PIPING MATERIALS AND |
| VALVING, CONFIRM THE EXISTING WATER HEATER IS FOR |
| OUTDOOR INSTALLATION AND SUBMIT WATER HEATER |
| INSTALLATION MANUAL. THIS IS A SECOND REQUEST. |
| 2. FBC 107.2.1 NOTE ON DRAWING SAYS SEE ATTACHED SPEC |
| FOR EXISTING WATER HEATER AND I FIND NONE UPLOADED TO |
| THE PROJECT FOR REVIEW. |
| 3. FBC FUEL GAS SECTION 404. PLEASE NOT THAT PIPING IN |
| CONCEALED LOCATIONS SHALL NOT HAVE UNIONS, TUBING |
| FITTINGS, RIGHT AND LEFT COUPLINGS, BUSHINGS, |
| COMPRESSION COUPLINGS AND SWING JOINTS MADE BY |
| COMBINATIONS OF FITTINGS UNLESS THE FITTINGS ARE LISTED |
| FOR USE IN CONCEALED LOCATIONS. |
| |
| REVIEWED REMOTELY BY JAMES BAKER, PE |