Plan Review Notes For Permit 20020275 |
Permit Number |
20020275 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-03-24 13:57:03 | 1. FBC 107.2.1 PROVIDE COMPLETE INSTALLATION PLAN | | DRAWING FOR RELOCATION OF EXISTING GAS WATER HEATER, | | INCLUDING GAS RISER DIAGRAM INCLUDING ANY OTHER | | EXISTING APPLIANCES AND BTUH VALUES, PIPE SIZING | | CRITERIA, WHERE EXISTING IS LOCATED, EXISTING PIPING ON | | PLAN, HOW IT IS TO BE RE ROUTED, PIPING MATERIALS AND | | VALVING, CONFIRM THE EXISTING WATER HEATER IS FOR | | OUTDOOR INSTALLATION AND SUBMIT WATER HEATER | | INSTALLATION MANUAL. THIS IS A SECOND REQUEST. | | 2. FBC 107.2.1 NOTE ON DRAWING SAYS SEE ATTACHED SPEC | | FOR EXISTING WATER HEATER AND I FIND NONE UPLOADED TO | | THE PROJECT FOR REVIEW. | | 3. FBC FUEL GAS SECTION 404. PLEASE NOT THAT PIPING IN | | CONCEALED LOCATIONS SHALL NOT HAVE UNIONS, TUBING | | FITTINGS, RIGHT AND LEFT COUPLINGS, BUSHINGS, | | COMPRESSION COUPLINGS AND SWING JOINTS MADE BY | | COMBINATIONS OF FITTINGS UNLESS THE FITTINGS ARE LISTED | | FOR USE IN CONCEALED LOCATIONS. | | | | REVIEWED REMOTELY BY JAMES BAKER, PE | | PX3997, PE77268 | | 561-805-6724 | | [email protected] | | | | | | |
|