2020-02-13 20:30:04ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. GARAGE DOOR OPENER RECEPTACLE REQUIRES GFCI
 PROTECTION THAT IS READILY ACCESSIBLE. NEC 210.8
  
 2. ATLEAST ONE GFCI RECEPTACLE OUTLET MUST BE INSTALLED
 PER CAR SPACE IN GARAGE. NEC 210.52G1
  
 3. DIGITALLY SUBMITTED PLANS MUST BE DIGITALLY SIGNED
 BY DESIGN PROFESSIONAL.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.