2020-02-14 11:29:03 | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | BUILDING REVIEW APPROVED WITH PROVISOS: | | | | 1) ONLY IMPACT RATED WINDOWS AND DOORS FROM THE | | APPROVED PRODUCT APPROVALS CAN BE USED. | | 2) A BLOWER DOOR TEST IS REQUIRED PER FBC EC R | | 402.4.1.2. | | 3) AT TIME OF ROOF FRAMING INSPECTION; PROVIDE, | | DESIGNER OF RECORD APPROVED, TRUSS ENGINEERING PACKAGE | | FOR BUILDING INSPECTOR. |
|