2020-03-23 16:13:00ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE L-401 THIS PAGE SHOWS A FEW PLANTERS WITH 120 VOLT
 LIGHTS IN THE PLANTERS, THESE WILL NEED TO BE GFCI
 PROTECTED BECAUSE OF THE LOCATION 680.22(B)(4)
  
 PAGE E3.0 SEEMS TO BE A DUPLICATE OF E1.0 AND BY A
 DIFFERENT ENGINEER. PLEASE CLARIFY
  
 GFCI PROTECTION FOR PUMPS WHERE IS IT LOCATED HOW MANY
 PUMPS? IF IN THE SET WHICH PAGE?