2020-07-08 11:42:19 | 1ST REVIEW FBC-2017 RES. PLUMBING |
| PERMIT- 20020232 |
| 7/8/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET P1: THE GAS WATER HEATER HAS BEEN REMOVED FROM |
| THE ACCESSORY BUILDING. INDICATE HOW HOT WATER IS TO BE |
| PROVIDED FOR BATHING, WASHING, AND CULINARY PURPOSES- |
| SECTION P2801.1 FBC RES. |
| |
| 2) P1 & P2- HOUSE BATH: CLARIFY THE LOCATION OF THE DRY |
| VENT CONNECTION FOR THE WET VENTED BATH FIXTURES- REFER |
| TO SECTION P3108.2.1 FBC RES- WHERE THE DRY VENT |
| CONNECTS TO A WATER CLOSET FIXTURE DRAIN, THE DRAIN |
| SHALL CONNECT HORIZONTALLY TO THE HORIZONTAL WET VENT |
| SYSTEM. NOT MORE THAN ONE WET-VENTED FIXTURE DRAIN |
| SHALL DISCHARGE UPSTREAM OF THE DRY-VENTED FIXTURE |
| DRAIN CONNECTION. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |