2020-04-17 17:36:24 | 2ND REVIEW FBC-2017 PLUMBING |
| PERMIT #20020232 |
| 4/17/20 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET P1 NOTE 9: PLEASE MODIFY THE NOTE TO INCLUDE |
| WATER HAMMER ARRESTORS FOR THE DISHWASHER AND ICE MAKER |
| LINES- SECTION P2903.5 FBC RES. |
| |
| 2) P1 NOTES: PLACE A NOTE TO INDICATE THE WATER SUPPLY |
| TO THE DISHWASHER SHALL BE PROTECTED AGAINST BACKFLOW |
| BY AN AIR GAP OR BACKFLOW PREVENTER- SECTION P2717 FBC |
| RES. |
| |
| 3) P1 NOTES: BECAUSE THERE ARE TWO SEPARATE DWELLINGS |
| TO BE CONSTRUCTED ON THE SAME LOT, PLEASE BE ADVISED |
| THAT INSTALLATION OF AN RPZ- TYPE BACKFLOW PREVENTER |
| WILL BE REQUIRED FOR THE WATER SERVICE PER THE CITY OF |
| WEST PALM BEACH CROSS CONNECTION MANUAL. |
| |
| 4) P1: PROVIDE EQUIPMENT SCHEDULES FOR THE WATER |
| HEATERS IN THE MAIN HOUSE AND ACCESSORY BUILDING. |
| SUBMIT MANUFACTURER'S SPECIFICATIONS AND PROVIDE ENERGY |
| COMPLIANCE DATA FOR THE UNITS IN THE ENERGY COMPLIANCE |
| REPORT- SEE SECTION C404.2 FBC EC. PLEASE NOTE THE |
| ORIGINAL ENERGY CALCULATION REPORT WAS NOT RESUBMITTED |
| WITH THE REVISED PLANS. |
| |
| 5) A2: PROVIDE A STORM DRAINAGE ISOMETRIC DRAWING |
| SHOWING PIPE SIZES, PIPE RUNS, VERTICAL TO HORIZONTAL |
| CONNECTIONS, DISCHARGE LOCATIONS, AND LOCATIONS OF |
| REQUIRED CLEANOUTS- SECTIONS 1106.2 & 1108.4 FBC P. |
| |
| 6) A1 & A2: PROVIDE A SUBMITTAL FOR THE SPRAY FOAM |
| INSULATION THAT WILL BE APPLIED TO THE STORM DRAIN |
| LEADERS AND PIPES- SECTION 107.2.1 WPB. |
| |
| 7) A2: MODIFY KEYNOTE #2 TO INDICATE THE SCUPPER |
| OPENING SHALL NOT BE LESS THAN 2" ABOVE THE ROOF |
| SURFACE- SECTION 1503.4.2.1 DFBC B. PLEASE PROVIDE A |
| SCUPPER DETAIL ON THE PLAN. |
| |
| 8) A2: PLACE A NOTE TO INDICATE COMPLIANCE WITH SECTION |
| 1101.7: ROOFS SHALL BE DESIGNED FOR THE MAXIMUM |
| POSSIBLE DEPTH OF WATER THAT WILL POND THEREON AS |
| DETERMINED BY THE RELATIVE LEVELS OF ROOF DECK AND |
| OVERFLOW WEIRS, SCUPPERS, EDGES OR SERVICEABLE DRAINS |
| IN COMBINATION WITH THE DEFLECTED STRUCTURAL ELEMENTS. |
| IN DETERMINING THE MAXIMUM POSSIBLE DEPTH OF WATER, ALL |
| PRIMARY ROOF DRAINAGE MEANS SHALL BE ASSUMED TO BE |
| BLOCKED. THE MAXIMUM POSSIBLE DEPTH OF WATER ON THE |
| ROOF SHALL INCLUDE THE HEIGHT OF THE WATER REQUIRED |
| ABOVE THE INLET OF THE SECONDARY ROOF DRAINAGE MEANS TO |
| ACHIEVE THE REQUIRED FLOW RATE OF THE SECONDARY |
| DRAINAGE MEANS TO ACCOMMODATE THE DESIGN RAINFALL RATE |
| AS REQUIRED BY SECTION 1106. |
| |
| 9) A0 & A2: PLACE A NOTE TO INDICATE THAT ENGINEERING |
| CERTIFICATION OF THE EXFILTRATION TRENCH WILL BE |
| PROVIDED AS A CONTINGENCY OF RECEIVING A FINAL CO FOR |
| THE BUILDING- SECTION 107.6 & 111.2 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |