2020-03-19 09:45:24 | 1ST REVIEW FBC-2017 PLUMBING |
| PERMIT #20020232 |
| 3/19/20 |
| |
| CODES IN EFFECT: |
| |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET P1: WATER HAMMER ARRESTORS ARE REQUIRED FOR |
| THE DISHWASHER AND WASHING MACHINE PER SECTION P2903.5 |
| FBC RES. |
| |
| 2) P1: THE WATER SUPPLY TO THE DISHWASHER SHALL BE |
| PROTECTED AGAINST BACKFLOW BY AN AIR GAP OR BACKFLOW |
| PREVENTER- SECTION P2717 FBC RES. |
| |
| 3) P1: PROVIDE THE CLEAR OPENING WIDTH OF THE SHOWER |
| DOORS IN THE MAIN HOUSE AND THE ACCESSORY BUILDING- |
| SECTION P2708.1.1 FBC RES. |
| |
| 4) P1: PLEASE INCLUDE THE COMBUSTION AIR CALCULATIONS |
| FOR THE WATER HEATER- SECTION G2407.5.1 FBC RES, AND |
| PROVIDE THE CORRECT CODE SECTION ON THE PLAN. |
| |
| 5) P1: PROVIDE THE MAKE AND MODEL OF THE GAS WATER |
| HEATER ON THE PLAN AND SUBMIT MANUFACTURER'S |
| SPECIFICATIONS- SECTION G2448.1 FBC RES. IF THE |
| APPLIANCE IS A DIRECT VENT PLEASE SHOW THE VENT AND AIR |
| INTAKE DUCT RUNS AND TERMINATION LOCATIONS ON THE PLAN- |
| SECTIONS G2427.2.1 & G2427.8(3) FBC RES. |
| |
| 6) P1: INDICATE HOW HOT WATER IS BEING PROVIDED TO THE |
| SINK AND SHOWER IN THE ACCESSORY BUILDING- P2801.1 FBC |
| RES. |
| |
| 7) P1: THE ENERGYGAUGE COMPLIANCE REPORT FORM R405-2017 |
| INDICATES A 40 GALLON STORAGE WATER HEATER WHICH IS NOT |
| SHOWN ON THE PLAN- SECTION R403.5.6 FBC RES. |
| |
| 8) BECAUSE THERE ARE TWO SEPARATE DWELLINGS TO BE |
| CONSTRUCTED ON THE SAME LOT, PLEASE BE ADVISED THAT |
| INSTALLATION OF AN RPZ-TYPE BACKFLOW PREVENTER WILL BE |
| REQUIRED FOR THE WATER SERVICE PER THE CITY OF WEST |
| PALM BEACH CROSS CONNECTION MANUAL. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |