Plan Review Notes
Plan Review Notes For Permit 20020232
Permit Number 20020232
Review Stop G
Sequence Number 1
Notes
Date Text
2020-04-20 07:23:382ND REVIEW FBC-2017 RESIDENTIAL GAS
 PERMIT #20020232
 4/20/2020
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 201
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P1: NOTE #4 & 10 INDICATE THE GAS WATER
 HEATER ON THE EXTERIOR OF BUILDING HOWEVER THE PLAN
 SHOWS THE WATER HEATER INSIDE THE UTILITY ROOM. A
 THOROUGH REVIEW OF THE PLANS CANNOT BE COMPLETED AT
 THIS TIME UNTIL THE EXACT LOCATION OF THE WATER HEATER
 IS CLARIFIED- SECTION 107.2.1 WPB.
  
 2) SHEETS A0 & P1: THE GAS ISOMETRIC DOES NOT APPEAR TO
 CORRESPOND WITH THE LOCATION OF THE METER ON THE SITE
 PLAN- SECTION 107.2.1 WPB.
  
 3) P1. GAS ISOMETRIC: PROVIDE THE TOTAL DEVELOPED
 LENGTH OF THE GAS PIPING RUN FROM THE POINT OF DELIVERY
 TO THE MOST REMOTE OUTLET- SECTIONS G2413.3 AND G2513.4
 FBC RES.
  
 4) P1. GAS ISOMETRIC: INDICATE WHICH TABLE FROM THE FBC
 RES WAS USED TO SIZE THE GAS PIPING. PLEASE REFER TO
 TABLES G2413.4(1) THROUGH G2413.4(21).
  
 5) PROVIDE AN EQUIPMENT SCHEDULE FOR THE WATER HEATER
 ON THE PLAN AND SUBMIT MANUFACTURER'S SPECIFICATIONS.
 PLEASE NOTE THAT A THOUGH REVIEW OF THE WATER HEATER
 INSTALLATION, GAS PIPING PLAN, AND COMBUSTION AIR AND
 VENTING OF THE APPLIANCE CANNOT BE COMPLETED AT THIS
 TIME.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  