2020-03-09 15:16:54 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PANEL AND FEEDER ARE UNDERSIZED FOR PANEL B IN THE |
| ACCESSORY STRUCTURE, BASED ON THE LOAD SPECIFIED. |
| DEMAND FACTORS SHOWN FOR PANEL B ARE NOT PERMITTED, |
| THEY ARE USED ONLY FOR SERVICES THAT SUPPLY 100% OF THE |
| LOAD. PROVIDE CORRECTION. FBC RE E3602.2, E3704.2 |
| 2. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| LOADS. THE METHOD FOR LOAD CALCULATION PROVIDED IS NOT |
| COMPLIANT WITH FBC RESIDENTIAL. FBC RE E3602.2 |
| 3. CIRCUIT A-12 FOR BATHROOM IS SHOWN AS A 15 AMP |
| CIRCUIT WITH A 14 GAUGE WIRE. A MINIMUM OF ONE 20 |
| AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY |
| BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE |
| NO OTHER OUTLETS. PROVIDE CORRECTION. FBC RE E3703.4 |
| 4. CIRCUIT A-14 IS SHOWN AS A BATHROOM CIRCUIT ON PLAN, |
| AND AS ONE OF THE FEEDERS FOR SUP-PANEL B IN THE PANEL |
| SCHEDULE. PROVIDE CORRECTION. WPB FBC 107.2.1 |
| 5. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED |
| PER CODE. FBC RE R314.3, R315.1; WPB FBC 107.2.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| |