2020-02-13 16:22:07 | 02/13/2020 E-MAIL FROM BRITNI (STORM ROOFING)I: |
| |
| 1. WE WILL BE USING A MEDIUM PATTY AS PER OUR PHONE |
| CONVERSATION. |
| 2. WE ARE SWITCHING THE UNDERLAYMENT FROM TU PLUS TO |
| THE POLYGLASS IRXE WHICH WILL GO DIRECT TO DECK, |
| FOLLOWED BY 30# FELT. I HAVE ATTACHED THE UPDATED |
| PRODUCT APPROVAL FOR THIS. |
| 3. WE ARE CHANGING THE PRODUCT APPROVAL TO THE |
| CERTAINTEED MODIFIED FOR TILE UNDERLAYMENT, PLEASE SEE |
| ATTACHED. |
| THANKS!!! |
| BRITNI |
| STORM ROOFING, INC. |
| 1340 53RD STREET, SUITE 8 |
| WEST PALM BEACH, FL 33407 |
| 561-689-0268 |
| 561-845-9182 FAX |
| [email protected] |
| |
| RESPONSE TO E-MAIL. |
| |
| 1- UNDERLAYMENT POLYGLASS IR-XE PROPOSED MAY NOT BE |
| APPROPRIATE FOR THE PROPOSED INSTALLATION. ACCORDING TO |
| TABLE 1 ON PAGE 4 OF 16 OF FLORIDA PRODUCT APPROVAL |
| FL5259-R29 THIS UNDERLAYMENT CAN NO BE USED FOR ROOF |
| TILE (NAIL-ON TILE OR FOAM-ON TILE). |
| |
| NOTE: |
| IF THE PURPOSE IS TO HAVE AN ADDITIONAL BASE LAYER THAT |
| IS DIRECTLY ADHERED TO THE ROOF DECK, THEN YOU MAY WANT |
| TO SEE IF SYSTEM #5 ON PAGE 6 OF 16 OF POLYGLASS TU |
| PLUS OF FLORIDA PRODUCT APPROVAL FL5259-R29 MAY WORK |
| FOR YOU. THIS IS AN APPROVED SYSTEM WITH HIGH DESIGN |
| PRESSURES THAT WORKS FOR THIS BUILDING LOCATION. AND, |
| MAY HAVE ALL THE PACKAGE YOUR CLIENT NEEDS. |
| OTHERWISE, A COMPLETE PROPOSED ASSEMBLY DOCUMENTATION |
| SUPPORTING HOW THE PROPOSED ASSEMBLY WILL WORK TO |
| COMPLY WITH SEC. 706.1 FBC-EXISTING BUILDING CAN BE |
| SUBMITTED FOR BUILDING OFFICIAL APPROVAL. THIS WILL BE |
| SUBMITTED AS AN ALTERNATIVE MATERIAL AND METHODS. SEC. |
| 104.11 CITY AMENDMENTS. |
| |
| 2- I APOLOGIZE, I FORGOT TO ASK YOU THE FIRST TIME. |
| SINCE THERE ARE SEVERAL BUILDINGS IN THIS PROPERTY, CAN |
| YOU PLEASE PROVIDE AN AERIAL VIEW FROM PAPA SHOWING |
| WHICH BUILDING AND ROOF AREA IS THE WORK TAKING PLACE. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |
| |