Date |
Text |
2020-02-10 09:36:27 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| 1- ROOF TILE FLORIDA PRODUCT APPROVAL FL17152-R3 AND |
| ROOF TILE ADHESIVE FLORIDA PRODUCT APPROVAL FL6332-R8 |
| SUBMITTED: CLEARLY MARK ADHESIVE PADDY SIZE AS REQUIRED |
| BY CITY POLICY FOR ALL ROOFING PERMITS TO VERIFY |
| COMPLIANCE WITH THE DESIGN PRESSURES OF SEC R301.2.1 |
| FBC-RESIDENTIAL. |
| |
| 2- ROOFING UNDERLAYMENT TU PLUS-MAX FLORIDA PRODUCT |
| APPROVALS FL5259-R29 SUBMITTED: |
| CLEARLY MARK WHICH MAXIMUM DESIGN PRESSURES ASSEMBLY |
| FROM SEC. 5.6.1 OF PRODUCT APPROVAL IS GOING TO BE |
| USED. OR IF USING THE FRSA/TRI APRIL 2012 (04-12) |
| REVISED EDITION, THEN PROVIDE COMPLETE INFORMATION |
| SHOWING THE DETERMINATION OF DESIGN WIND LOADS AND |
| UNDERLAYMENT FASTENING AS REQUIRED BY SEC. 5.6.1 OF |
| PRODUCT APPROVAL SUBMITTED. |
| |
| 3- IT IS NOT CLEAR WHY SUBMITTING FLAT ROOF FLORIDA |
| PRODUCT APPROVAL FL16709-R6. COVER PAGE STATES "PG 3 OF |
| 4 MODIFIED FOR THE UNDERLAYMENT ONLY". IS THIS THE |
| UNDERLAYMENT FOR THE TILE ROOF?. IF SO, THIS IS A FLAT |
| ROOF ASSEMBLY NOT AN UNDERLAYMENT FOR ROOF TILE. THE |
| UNDERLAYMENT FOR THE ROOF TILE IS THE TU PLUS PRODUCT |
| APPROVAL SUBMITTED. SEC. 107.2.1 CITY AMENDMNTS. |
| |
| ON THE OTHER HAND, IF THERE IS A FLAT ROOF IN THIS ROOF |
| , THEN CLEARLY MARK WHICH APPROVED ASSEMBLY IS GOING TO |
| BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN |
| PRESSURES OF SEC. R301.2.1 FBC-RESIDENTIAL. |
| |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |
| |