Plan Review Notes For Permit 20020205 |
Permit Number |
20020205 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-02-12 13:15:35 | SHUTTERS | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | | | CORRECTIONS NEEDED - | | 1. FBC R 301, COMPLETE THE FORM PROVIDED AT THE FRONT | | COUNTER "SCHEDULE FOR INSTALLATION OF OPENING | | PROTECTIVE DEVICES" OR PROVIDE ALL INFORMATION REQUIRED | | IN ANOTHER FORMAT (SUCH AS EXCEL SPREADSHEET) | | | | 2. WHEN COMPLETING THE INSTALLATION SCHEDULE, PLEASE | | NOTE FACTORS APPLY DEPENDING ON SUBSTRATE, EDGE | | DISTANCE AND FASTENER. FOR FASTENER, IF USING TAPCON, | | BE SPECIFIC AS TO WHICH TAPCON (TAPCON W/ADVANCED | | THREADFORM TECHNOLOGY REQUIRES A .9 FACTOR). | | | | 3. WIND DESIGN PRESSURES NEED TO BE BASED ON "EXPOSURE | | "C" " NOT "B" AS SHOWN ON YOUR BUILDING INFORMATION | | DOCUMENT | | | | 4. PLEASE SHOW THE DISTANCE FROM THE EDGE OF THE WINDOW | | TO THE EDGE OF THE BUILDING - FOR THE WINDOWS NEXT TO | | THE CORNERS - NEEDED TO DETERMINE WIND ZONE 4 OR 5. |
|