Plan Review Notes
Plan Review Notes For Permit 20020205
Permit Number 20020205
Review Stop B
Sequence Number 1
Notes
Date Text
2020-02-12 13:15:35SHUTTERS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
 1. FBC R 301, COMPLETE THE FORM PROVIDED AT THE FRONT
 COUNTER "SCHEDULE FOR INSTALLATION OF OPENING
 PROTECTIVE DEVICES" OR PROVIDE ALL INFORMATION REQUIRED
 IN ANOTHER FORMAT (SUCH AS EXCEL SPREADSHEET)
  
 2. WHEN COMPLETING THE INSTALLATION SCHEDULE, PLEASE
 NOTE FACTORS APPLY DEPENDING ON SUBSTRATE, EDGE
 DISTANCE AND FASTENER. FOR FASTENER, IF USING TAPCON,
 BE SPECIFIC AS TO WHICH TAPCON (TAPCON W/ADVANCED
 THREADFORM TECHNOLOGY REQUIRES A .9 FACTOR).
  
 3. WIND DESIGN PRESSURES NEED TO BE BASED ON "EXPOSURE
 "C" " NOT "B" AS SHOWN ON YOUR BUILDING INFORMATION
 DOCUMENT
  
 4. PLEASE SHOW THE DISTANCE FROM THE EDGE OF THE WINDOW
 TO THE EDGE OF THE BUILDING - FOR THE WINDOWS NEXT TO
 THE CORNERS - NEEDED TO DETERMINE WIND ZONE 4 OR 5.