Date |
Text |
2020-02-27 14:14:07 | RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW |
| CHECKLIST. |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| ORIGINAL COMMENT: |
| 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL16730-R24 |
| SUBMITTED: CLEARLY MARK WHICH APPROVED ASSEMBLY IS |
| GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. NOTE: |
| IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN |
| PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED |
| RAS 117 CALCULATIONS ARE REQUIRED. |
| |
| RESPONSE: |
| IT IS NOT CLEAR WHICH APPROVED ASSEMBLY IS GOING TO BE |
| INSTALLED. ENGINEER IS REFERENCING AND OLD FLORIDA |
| PRODUCT APPROVAL FL16730-R22. ENGINEER IS SPECIFYING |
| SYSTEM W-56 ON PAGE 14 OF 100. ACCORDING TO THE OLD |
| FLORIDA PRODUCT APPROVAL, THIS IS A NON-INSULATED |
| SYSTEM. FLORIDA PRODUCT APPROVAL THAT WAS SUBMITTED IS |
| FL16730-R24 AND IS MARKED WITH ASSEMBLY W-54 WHICH IS |
| AN INSULATED ASSEMBLY. REVISE AS REQUIRED TO MATCH. |
| NOTE: ENGINEER NEEDS TO REFERENCE THE CURRENT FLORIDA |
| PRODUCT APPROVAL FL 16730-R24 TO AVOID CONFLICTS |
| DELAYS. RE-SUBMIT REVISED RAS 117 CALCULATIONS SHOWING |
| THE CORRECT ASSEMBLY. SEC. 107.2.1 CITY AMENDMENTS. |
| (PROVIDE 2 COPIES. ONLY ONE WAS SUBMITTED). |
| |
| 2- OK. |
| |
| 3- OK. |
| |
| 4- OK |
| |
| 5- OK. |
| |
| |
| PROVISO: |
| 8/12 ROOF TILE SLOPE REQUIRES EVERY TILE TO BE FASTENED |
| IN ADDITION TO THE ADHESIVE. SEE PAGE 9 OF FRSA/TRI 5TH |
| EDITION REVISED AND SEC. R905.3.2 FBC-RESIDENTIAL. |
| |
| |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |