Plan Review Notes
Plan Review Notes For Permit 20020196
Permit Number 20020196
Review Stop B
Sequence Number 2
Notes
Date Text
2020-02-21 16:12:02RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL16730-R24
 SUBMITTED: CLEARLY MARK WHICH APPROVED ASSEMBLY IS
 GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. NOTE:
 IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 RESPONSE:
 IT IS NOT CLEAR WHICH APPROVED ASSEMBLY IS GOING TO BE
 INSTALLED. ENGINEER IS REFERENCING AND OLD FLORIDA
 PRODUCT APPROVAL FL16730-R22. ENGINEER IS SPECIFYING
 SYSTEM W-56 ON PAGE 14 OF 100. ACCORDING TO THE OLD
 FLORIDA PRODUCT APPROVAL, THIS IS A NON-INSULATED
 SYSTEM. FLORIDA PRODUCT APPROVAL THAT WAS SUBMITTED IS
 FL16730-R24 AND IS MARKED WITH ASSEMBLY W-54 WHICH IS
 AN INSULATED ASSEMBLY. REVISE AS REQUIRED TO MATCH.
 NOTE: ENGINEER NEEDS TO REFERENCE THE CURRENT FLORIDA
 PRODUCT APPROVAL FL 16730-R24 TO AVOID CONFLICTS
 DELAYS. RE-SUBMIT REVISED RAS 117 CALCULATIONS SHOWING
 THE CORRECT ASSEMBLY. SEC. 107.2.1 CITY AMENDMENTS.
 (PROVIDE 2 COPIES. ONLY ONE WAS SUBMITTED).
  
 2- OK.
  
 3- OK.
  
 4- OK
  
 5- OK.
  
  
 PROVISO:
 8/12 ROOF TILE SLOPE REQUIRES EVERY TILE TO BE FASTENED
 IN ADDITION TO THE ADHESIVE. SEE PAGE 9 OF FRSA/TRI 5TH
 EDITION REVISED AND SEC. R905.3.2 FBC-RESIDENTIAL.
  
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  