Plan Review Notes
Plan Review Notes For Permit 20020170
Permit Number 20020170
Review Stop M
Sequence Number 1
Notes
Date Text
2020-02-18 10:45:391ST REVIEW FBC-2017 MECHANICAL
 PERMIT
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M101: THE PREVIOUSLY UNCONDITIONED STORAGE
 BUILDING SHALL BE IN FULL COMPLIANCE WITH THE FLORIDA
 ENERGY CONSERVATION CODE- 2017 SIXTH EDITION. PLEASE
 SUBMIT A COMPLIANCE REPORT- SECTION C101.5 FBC EC.
  
 2) M101: PLEASE CLARIFY WHY THE BUILDING IS BEING
 CONDITIONED. PROVIDE A BRIEF NARRATIVE DESCRIBING THE
 USE OF THE STORAGE SPACES. PLEASE NOTE THAT CHANGES OF
 OCCUPANCY SHALL COMPLY THE FLORDIA EXISTING BUILDING
 CODE- 2017 SIXTH EDITION (SECTION 101.2 FBC EX) AND MAY
 REQUIRE A FL. LICENSED DESIGN PROFESSIONAL TO PROVIDE
 PLANS AND SPECIFICATIONS.
  
 3) M101: IT APPEARS THAT THE STORAGE SPACES HAVE GARAGE
 BAY DOORS WHICH INDICATES VEHICLES MAY BE STORED IN THE
 SPACES. REFER TO TABLE 403.3.1.1 AND SECTION 404:
 EXHAUST VENTILATION SYSTEMS REQUIRED.
  
 4) M101: THE SUBMITTED AC HEAT LOAD CALCULATIONS DO NOT
 INDICATE BAY DOORS ON THE INPUT DATA SHEET- SECTION
 C403.2.1 FBC EC.
  
 5) M101: THE CORRIDOR SHALL NOT BE USED TO RETURN AIR
 TO THE AIR HANDLER. PROVIDE DUCTED RETURNS- SECTION
 601.2 FBC M.
  
 6) PROVIDE AN ELECTRICAL PLAN AND ELECTRICAL SUB-PERMIT
 APPLICATION- SECTION 107.2.1 WPB.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  