Date |
Text |
2020-05-01 10:54:12 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| |
| THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| INSPECTION. |
| |
| |
| |
| 1) SHEET 1.0A - THE FRONT DOORS INDICATED AS 1 IN THE |
| DOOR SCHEDULE HAS A DEADBOLT LOCK. |
| |
| PER NFPA 101 , CH 38 NEW BUSINESS OCCUPANCIES AND CH 7, |
| MEANS OF EGRESS: |
| |
| 38.2.2.2 DOORS. |
| 38.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE |
| PERMITTED. |
| 38.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE |
| PERMITTED |
| ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS. |
| |
| 7.2.1.5.5 KEY-OPERATED LOCKS. |
| 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE |
| PERMITTED TO HAVE |
| KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT |
| ALL OF THE |
| FOLLOWING CRITERIA ARE MET: |
| (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11 |
| THROUGH 43 FOR |
| THE SPECIFIC OCCUPANCY. |
| (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS |
| THAN 1 IN. |
| (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS |
| FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF: |
| THIS |
| DOOR TO REMAIN UNLOCKED WHEN THE |
| BUILDING IS OCCUPIED. |
| (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY |
| DISTINGUISHABLE |
| AS LOCKED. |
| (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT |
| INSIDE THE |
| BUILDING WHEN IT IS LOCKED. |
| |
| PLEASE REVIEW AND ENSURE COMPLIANCE. |
| |
| |
| |
| 2) SHEET 1.0A - THE REAR EXIT DOOR INDICATED AS 2 IN |
| THE DOOR SCHEDULE HAS A DEAD BOLT. |
| |
| PER NFPA 101 , CH 38 NEW BUSINESS OCCUPANCIES AND CH 7, |
| MEANS OF EGRESS: |
| |
| 38.2.2.2 DOORS. |
| 38.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE |
| PERMITTED. |
| 38.2.2.2.2* LOCKS COMPLYING WITH 7.2.1.5.5 SHALL BE |
| PERMITTED |
| ONLY ON PRINCIPAL ENTRANCE/EXIT DOORS. |
| |
| 7.2.1.5.5 KEY-OPERATED LOCKS. |
| 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE |
| PERMITTED TO HAVE |
| KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT |
| ALL OF THE |
| FOLLOWING CRITERIA ARE MET: |
| (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11 |
| THROUGH 43 FOR |
| THE SPECIFIC OCCUPANCY. |
| (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS |
| THAN 1 IN. |
| (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS |
| FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF: |
| THIS |
| DOOR TO REMAIN UNLOCKED WHEN THE |
| BUILDING IS OCCUPIED. |
| (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY |
| DISTINGUISHABLE |
| AS LOCKED. |
| (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT |
| INSIDE THE |
| BUILDING WHEN IT IS LOCKED. |
| |
| PLEASE REVIEW AND ENSURE COMPLIANCE. |
| |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |