Plan Review Notes
Plan Review Notes For Permit 20020168
Permit Number 20020168
Review Stop E
Sequence Number 1
Notes
Date Text
2020-03-01 13:26:49CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ORIGINAL PLANS FOR PERMIT 18081402 SHOW A 200 AMP
 AUTOMATIC TRANSFER SWITCH CONNECTED TO THE GENERATOR AS
 PART OF THE RISER DIAGRAM. THIS DRAWING DOES NOT SHOW
 AN ATS. PROVIDE CLARIFICATION AND/OR CORRECTIONS. WPB
 FBC 107.2.1
 2. ORIGINAL PLANS FOR PERMIT 18081402 SHOW 1/0 SIZE
 FEEDERS IN THE GUTTER TO METER CAN, AND FROM METER CAN
 TO DISCONNECT. THE PROVIDED PLAN STATES THAT THE
 FEEDERS TO THE PANEL WILL BE REPLACED, BUT IS SILENT IN
 REGARDS TO THESE CONDUITS. PROVIDE CORRECTION. NEC
 310.15(B)(16); WPB FBC 107.2.1
 3. PLAN DOES NOT STATE WHICH TENANT SPACE THIS BUILD
 OUT WILL OCCUPY. PROVIDE CORRECTION. WPB FBC 107.2.1
 4. PROVIDE UPDATED AIC CALCULATIONS AND NOTES FOR
 STICKERS WITH CHANGE IN WIRE SIZE. NEC 110.9, 110.10,
 110.16, 110.24; WPB FBC 107.2.1
 5. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 310.15, 408.30
 6. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 7. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  