2020-02-25 13:53:51 | 2/25/2020 1ST PLUMBING/POOL REVIEW **DENIED** WITH |
| COMMENTS NOTE - A COMPREHENSIVE REVIEW COULD NOT BE |
| DONE AT THIS TIME AND ADDITIONAL PLAN REVIEW COMMENTS |
| MAY BE GENERATED UPON THE RE-REVIEW OF SUBMITTED |
| CORRECTIONS. |
| |
| 1- SUBMIT DOCUMENTATION THAT THE GAS POOL HEATER MEETS |
| THE MINIMUM REQUIRED EFFICIENCY AS REQUIRED BY THE 2017 |
| FBC-ENERGY SEC.R403.10.4 |
| |
| 2- SWIMMING POOL HEAT PUMP POOL HEATERS SHALL HAVE A |
| MINIMUM COP OF 4.0 WHEN TESTED IN ACCORDANCE WITH AHRI |
| 1160. |
| |
| 3- ALL POOL HEATERS SHALL BE EQUIPPED WITH A READILY |
| ACCESSIBLE ON-OFF SWITCH THAT IS MOUNTED OUTSIDE THE |
| HEATER TO ALLOW SHUTTING OFF THE HEATER WITHOUT |
| ADJUSTING THE THERMOSTAT SETTING. 2017 FBC-ENERGY ? |
| SEC. R403.10.1 |
| |
| 4- HEATED SWIMMING POOLS AND IN GROUND PERMANENTLY |
| INSTALLED SPAS SHALL BE EQUIPPED WITH A VAPOR-RETARDANT |
| COVER ON OR AT THE WATER SURFACE OR A LIQUID COVER OR |
| OTHER MEANS PROVEN TO REDUCE HEAT LOSS. 2017 FBC- |
| ENERGY- SEC. R 403.10.3. |
| |
| 5- THE DYNAMIC HEAD CALCULATIONS FOR THE MAXIMUM SYSTEM |
| FLOW DOES NOT SHOW ALL FRICTION LOSS THROUGH ALL |
| HEATERS. WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 6- BACKFLOW PREVENTER REQUIRED PER THE CITY OF WEST |
| PALM BEACH ORD #2853-95. A PERMIT REQUIRED BY A |
| LICENSED CONTRACTOR AND MUST BE CERTIFIED BY UTILITIES |
| PRIOR TO FINAL INSPECTION. A DUAL CHECK VALVE MAY BE |
| USED IF NO POOL FILL IS INSTALLED AT THE METER AND |
| INSTALLED BY UTILITIES WHICH DO NOT REQUIRE A PERMIT SO |
| PLEASE CONTACT CITY OF WPB UTILITIES AT 561-822-2240 |
| FOR FURTHER DIRECTIONS. |
| |
| 7- A CONTRACTOR LICENSED UNDER STATUES 489 SEPERATE |
| PERMIT IS REQUIRED FOR THE GAS AND PLUMBING |
| |
| 8- SHOW THE BTU LOAD FOR THE GAS POOL HEATER. THIS |
| VALUE MUST BE INCLUDED IN THE SIZING OF THE SYSTEM. |
| 2017 FBC FUEL GAS SEC. 402.2 OR 2017 FBC FUEL GAS RES. |
| SEC G2413.2 MAXIMUM GAS DEMAND |
| |
| 9- THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON |
| THE APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED |
| CONTRACT AND SHALL INCLUDE DEMO OF EXISTING POOL. WPB |
| AMENDMENTS TO THE FBC 109.3. BUILDING PERMITS |
| VALUATIONS. |
| |
| 10- GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED |
| IN THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT |
| BEEN PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND |
| PLANS WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE |
| RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT |
| REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE. AT |
| THIS TIME. WPB AMENDMENTS TO FBC SEC. 107.2.1. |
| |