Plan Review Notes
Plan Review Notes For Permit 20020104
Permit Number 20020104
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-02-11 09:52:39THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) IN LIEU OF REQUIRED REMOVAL OF SPRINKLERS CLEAR
 SIGNAGE IN MULTIPLE LOCATIONS WILL BE REQUIRED STATING
 THE SYSTEM IS INACTIVE.
  
  
 27.2* INACTIVE SPRINKLER SYSTEMS ABANDONED IN PLACE.
 27.2.1 WHERE ALL OR PART OF AN INACTIVE SPRINKLER
 SYSTEM IS
 ABANDONED IN PLACE, COMPONENTS INCLUDING SPRINKLERS,
 HOSE
 VALVES AND HOSES, AND ALARM DEVICES SHALL BE REMOVED.
 27.2.2 CONTROL VALVES ABANDONED IN PLACE SHALL HAVE THE
 OPERATING
 MECHANISMS REMOVED.
 27.2.3 SPRINKLER SYSTEM PIPING AND/OR VALVES ABANDONED
 IN
 PLACE SHALL BE UNIQUELY IDENTIFIED TO DIFFERENTIATE
 THEM FROM
 ACTIVE SYSTEM PIPING AND VALVES.
  
 PLEASE ENSURE COMPLIANCE AND COORDINATE SIGN LOCATION
 WITH THE FIRE INSPECTOR.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  