2020-02-06 06:56:1202/06/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE SHOW HOW YOU DETERMINE THE SIZE OF THE GREASE
 TRAP PRESUMING YOU ARE USING 14 LB. GREASE CAPACITY,
 (7) GALLONS PER MINUTE RATE FLOW THIS UNIT SHALL BE
 SIZED IN ACCORDANCE WITH THE SIZING REQUIREMENTS PER
 THE 2017 FBC SEC P 1003.3.4 AND TABLE 1003.3.4.1.
  
 2. ISOMETRIC SHOWS ALL SINKS MANIFOLDED TOGETHER PLEASE
 SEPARATE PER THE 2017 FBC SEC. 802.1.1.
  
 EXAMPLE 8-2
 ASSUME A SINGLE-FIXTURE INSTALLATION. SIZE THE GREASE
 INTERCEPTOR FOR A THREE-COMPARTMENT POT (SCULLERY)
 SINK, WITH EACH COMPARTMENT BEING 18 ? 24 ? 12 INCHES.
  
 1. DETERMINE THE SINK VOLUME:
 ? CUBIC CONTENTS OF ONE SINK COMPARTMENT = 18 ? 24 ? 12
 = 5,184 IN.3
 ? CUBIC CONTENTS OF THREE SINK COMPARTMENTS = 3 ? 5,184
 = 15,552 IN.3
 ? CONTENTS EXPRESSED IN GALLONS = 15,552 IN.3/231 =
 67.3 GAL
 2. ADD THE TOTAL POTABLE WATER SUPPLY THAT COULD BE
 DISCHARGED INDEPENDENT OF THE FIXTURE CALCULATED ABOVE,
 INCLUDING MANUFACTURER-RATED APPLIANCES SUCH AS WATER
 WASH EXHAUST HOODS.
 3. DETERMINE THE FIXTURE LOAD. A SINK (OR FIXTURE)
 SELDOM IS FILLED TO THE BRIM, AND DISHES, POTS, OR PANS
 DISPLACE APPROXIMATELY 25 PERCENT OF THE WATER.
 THEREFORE, 75 PERCENT OF THE ACTUAL FIXTURE CAPACITY
 SHOULD BE USED TO ESTABLISH THE DRAINAGE LOAD: 0.75 ?
 67.3 GAL = 50.8 GAL.
 4. CALCULATE THE FLOW RATE BASED ON DRAIN TIME,
 TYPICALLY ONE OR TWO MINUTES. FLOW RATE IS CALCULATED
 BY DIVIDING THE DRAINAGE LOAD IN GALLONS BY THE DRAIN
 TIME IN MINUTES. THEREFORE, THE FLOW FOR THIS EXAMPLE
 WOULD BE 50 GPM (3.15 L/S) FOR ONE-MINUTE DRAINAGE OR
 25 GPM (1.58 L/S) FOR TWO-MINUTE DRAINAGE.
 5. SELECT A HYDROMECHANICAL INTERCEPTOR WITH A RATED
 CAPACITY OF 50 GPM FOR ONE-MINUTE FLOW OR 25 GPM FOR
 TWO-MINUTE FLOW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  