Plan Review Notes
Plan Review Notes For Permit 20020087
Permit Number 20020087
Review Stop P
Sequence Number 1
Notes
Date Text
2020-02-12 13:29:461) SUBMIT AN ISOMETRIC DRAWING SHOWING HOW THE DRAIN
 FOR THE WASHING MACHINE AND THE KITCHEN SINK WILL BE
 CONNECTED TO THE EXISTING 3 INCH STACK. THE SUBMITTED
 DRAWING IS VAGUE.WPB AMEND. TO FBC SEC. 107.3.5.1.3.
 2) SUBMIT A WATER RISER DIAGRAM.WPB AMEND. TO FBC SEC.
 107.3.5.1.3.
 3) AIR ARRESTORS WILL BE REQUIRED ON THE WATER LINES
 FOR THE WASHER.
 4) SHUT OFF VALVES FOR THE WASHER SHALL BE ACCESSIBLE.
 WILL THE WATER SUPPLY VALVES FOR THE WASHER /DRYER BE
 BEHIND THE UNIT? IS THIS A STACKED WASHER /DRYER UNIT?
 CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW