Plan Review Notes For Permit 20020087 |
Permit Number |
20020087 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-02-12 13:29:46 | 1) SUBMIT AN ISOMETRIC DRAWING SHOWING HOW THE DRAIN | | FOR THE WASHING MACHINE AND THE KITCHEN SINK WILL BE | | CONNECTED TO THE EXISTING 3 INCH STACK. THE SUBMITTED | | DRAWING IS VAGUE.WPB AMEND. TO FBC SEC. 107.3.5.1.3. | | 2) SUBMIT A WATER RISER DIAGRAM.WPB AMEND. TO FBC SEC. | | 107.3.5.1.3. | | 3) AIR ARRESTORS WILL BE REQUIRED ON THE WATER LINES | | FOR THE WASHER. | | 4) SHUT OFF VALVES FOR THE WASHER SHALL BE ACCESSIBLE. | | WILL THE WATER SUPPLY VALVES FOR THE WASHER /DRYER BE | | BEHIND THE UNIT? IS THIS A STACKED WASHER /DRYER UNIT? | | CLARIFY. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|