Plan Review Notes For Permit 20020077 |
Permit Number |
20020077 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-02-07 07:52:07 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | BUILDING REVIEW DENIED: | | | | FBC R TABLE R301.2(2) THE WIND LOADS FOR ZONE 3 IN | | EXPOSURES B AND C BOTH EXCEED THE MAXIMUM DESIGN | | PRESSURE FOR THE FLAT ROOF BASE SHEET. AS PER | | LIMITATION # 7 OFTHE SUBMITTED NOA, PLEASE PROVIDE A | | DESIGN PROFESSIONAL'S SIGNED/SEALED FASTENING PATTERN | | WITH CALCULATIONS. |
|